WARNING
Danger electrical voltage!
» The entire unit must be disconnected from the mains during check and replacement!
» Observe the 5 Security Rules!
The condition of the sacrificial anode can be verified by a protective current measurement with an amperemeter.
Procedure:
"
Remove the front and the left panel to access to the storage tank.
"
Lift the black tank cover
"
Remove the black tank cover and the sealing.
Access to the anode connection 1 ¼“.
"
Disconnect the potential equalisation cable from the tank.
"
Connect an amperemeter between anode and tank.
With a protective current of < 0.3 mA, the anode must be removed, checked for erosion and replaced if necessary!
"
If the sacrificial anode is highly corroded and nearly disintegrated, change the anode.
(Sacrificial anode change see
Service
)
41
Genius - V 1.0
Maintenance / Remedying Faults