6 - 3
6 Maintenance
NA-series Programmable Terminal Hardware User’s Manual (V117)
6-
1 Period
ic Main
tena
nce an
d In
spect
ion
6
6-
1-2 Per
iodic Insp
ection
*1. The ambient temperature and ambient humidity criteria depend on conditions. Refer to
Required Tools
• Phillips-head screwdriver
• Voltage tester or digital multi-meter
• Industrial alcohol and clean cotton cloth
Tools Required Occasionally
• Thermometer and hygrometer (humidity meter)
2
Ambient
environ-
ment
Check for accumulation of dirt,
dust, salt, metal powder, etc.
No accumulation
Clean and protect the NA Unit if
necessary.
Check for water, oil, or chemi-
cal sprays that may land on the
NA Unit.
No spray
Clean and protect the NA Unit if
necessary.
Check for corrosive or flamma-
ble gases in the area of the NA
Unit.
No corrosive or flam-
mable gases
Check by smell or use a sensor.
Check for direct vibration or
shock placed on the NA Unit.
Vibration resistance
and shock resistance
must be within specifi-
cations.
Install cushioning or shock absorb-
ing equipment if necessary.
Check for noise sources near
the NA Unit.
No noise source
Either separate the NA Unit away
from noise source or protect the
NA Unit.
3
Installa-
tion and
wiring
Check the mounting brackets
to see if they are loose.
No looseness
Tighten loose screws with a Phil-
lips-head screwdriver.
Check that cable connectors
are fully inserted and locked.
No looseness
Fully insert and lock the connector
Check for loose screws in
external wiring.
No looseness
Tighten loose screws with a Phil-
lips-head screwdriver.
Check crimp connectors in
external wiring.
Adequate spacing
between connectors
Check visually and adjust if neces-
sary.
Check for damaged external
wiring cables.
No visible damage
Check visually and replace cables
if necessary.
4
User-ser
viceable
parts
Check the brightness of the
backlight.
The backlight must be
sufficiently bright.
Backlight life (at room
temperature and
humidity): 50,000 hours
Contact your OMRON representa-
tive to request replacement.
Check whether the
CJ1W-BAT01 Battery Set has
reached its service life or
whether it is passed the expira-
tion date.
Service life expectancy
is 5 years.
Replace the Battery when its ser-
vice life expectancy has passed
even if a Battery error has not
occurred.
5
Touch
panel
position
input
accuracy
Are the touched positions and
the positions that respond off-
set?
The positions must not
be offset.
Calibrate the touch panel with the
System Menu.
Tools Required for Inspections
No.
Item
Inspection
Criteria
Correction
Summary of Contents for OMRON NA Series
Page 8: ...Sections in this Manual 6 NA series Programmable Terminal Hardware User s Manual V117...
Page 12: ...CONTENTS 10 NA series Programmable Terminal Hardware User s Manual V117...
Page 34: ...Revision History 32 NA series Programmable Terminal Hardware User s Manual V117...
Page 82: ...3 Installation and Wiring 3 22 NA series Programmable Terminal Hardware User s Manual V117...
Page 164: ...5 Troubleshooting 5 18 NA series Programmable Terminal Hardware User s Manual V117...
Page 179: ...I 1 I NA series Programmable Terminal Hardware User s Manual V117 Index...
Page 181: ......