3 Installation and Wiring
3 - 12
NA-series Programmable Terminal Hardware User’s Manual (V117)
Precautions for Correct Use
Observe the following precautions to prevent broken wires.
• When you remove the sheath, be careful not to damage the conductor.
• Connect the conductor without twisting the wires.
• Do not weld the conductors. If you do so, vibration may cause the wires to break.
• Do not pull on the cables or bend the cables beyond their natural limit.
Do not place heavy objects on top of the cables or other wiring lines. Doing so may break the
cables.
• Before you insert a wire into a terminal hole, turn the screw that tightens the terminal counter-
clockwise until the terminal is no longer visible. Then, insert the wire so that it is held on the
terminal and screw side of the case and turn the screw clockwise to tighten the terminal.
• Faulty contact will result if you turn the screw counterclockwise to secure the wire. If neces-
sary, remove the wire, make sure it is inserted in the terminal hole, and then connect it again.
The NA Unit has a functional ground terminal (
). Wire the functional ground terminal according to
the following conditions.
• If there is a difference in electrical potential between the NA Unit and the connected devices, ground
them as shown in the following figure.
Precautions for Safe Use
Ground the NA Unit correctly.
Precautions for Correct Use
If the connected devices are separated too far from the NA Unit to ground them to the same
point and the NA Unit is installed in the same panel as devices that generate noise (such as
motors and inverters), do not ground the NA Unit.
Grounding
Clockwise Counterclockwise
Ground to
one point.
Summary of Contents for OMRON NA Series
Page 8: ...Sections in this Manual 6 NA series Programmable Terminal Hardware User s Manual V117...
Page 12: ...CONTENTS 10 NA series Programmable Terminal Hardware User s Manual V117...
Page 34: ...Revision History 32 NA series Programmable Terminal Hardware User s Manual V117...
Page 82: ...3 Installation and Wiring 3 22 NA series Programmable Terminal Hardware User s Manual V117...
Page 164: ...5 Troubleshooting 5 18 NA series Programmable Terminal Hardware User s Manual V117...
Page 179: ...I 1 I NA series Programmable Terminal Hardware User s Manual V117 Index...
Page 181: ......