BackupStore 5000
Routine Maintenance
4 Guide to the Routine Maintenance On the Management
Software
Issue 01 (2010-03-26)
Symantec Corporation
4-13
Figure 4-12
Power supply state
Table 4-7
Description of parameters related to the power supply state
Parameter
Description
Status
The running state of the power supply.
Presence detected
indicates that the power supply works
normally.
Failure detected
indicates that the power supply is absent or
faulty.
Wattage
The power value of the power supply. Unit:
Watts
.
Exception Handling
If the power supply is in the
Failure detected
state, see
PEM Alarm
in the
NetBackup 5000
Troubleshooting
.
4.7 Checking Miscellaneous Information
This section describes how to check the miscellaneous information on the system monitoring
interface.
Impact on the System
None.
Reference Standard
The temperature at the inner inlet of the chassis should be lower than
45°C
.
The normal state of
Chassis Intrusion
is
inactive
.
The system monitoring interface displays information about the RAID card battery, and
the temperature of the RAID card battery should be lower than
40°C
.
Procedure
Step 1
Log in to the system monitoring interface. For the detailed procedure, see
the System Monitoring Interface
Step 2
Expand the node in the navigation tree, and then click
Miscellaneous Information
, as shown
in