Operating Instructions
42
3
4
2
1
Fig. 36: Details for inlet size
1 Reference plane
2 Measuring value, max. measuring range
3 Antenna length
4 Useful measuring range
Output value
Output signals
4 … 20 mA/HART - active; 4 … 20 mA/HART - passive
Passive terminal voltage
9 … 30 V DC
Short-circuit protection
Provided
Electrical isolation
Provided
Signal resolution
0.3 μA
Current output failure signal (adjustable)
mA value unchanged, 20.5 mA, 22 mA, < 3.6 mA
Max. output current
22 mA
Starting current
≤
3.6 mA
Load (4 … 20 mA/HART - active)
< 500
Ω
Damping (63 % of input value)
0 … 999 s, adjustable
Measurement accuracy (to DIN EN 60770-1)
Process reference conditions to DIN EN 61298-1
- Temperature
+18 - +30 °C (+64 - +86 °F)
- Relative humidity
45 - 75 %
- Air pressure
860 - 1060 mbar / 86 - 106 kPa (12.5 - 15.4 psig)
Installation reference conditions
- Minimum distance from components
> 200 mm (7.874 in)
- Reflector
Flat panel reflector
- Interference reflections
Max. interference signal 20 dB less than useful echo
Measurement deviation for solids
The values are heavily dependent on the application.
It is therefore not possible to provide binding details.
Measurement deviation under
≤
±30 mm
EMC influence