20.4 Electrical Data
20.4.1 Air Handling Unit
MIN. POWER SUPPLY
COMPACT
Air:
1-phase, 3-wire, 230 V -10/+15%, 50 Hz, 10 AT
COMPACT
Heat:
3-phase, 5-wire, 400 V -10/+15%, 50 Hz, 16 AT
20.4.2 Fans
RATED DATA PER FAN
COMPACT Air and COMPACT Heat
Size 02:
1 x 230 V, 50/60 Hz, 0.4 kW (0.24 kW)*
Size 03:
1 x 230 V, 50/60 Hz, 0.4 kW
*) The motor controls limit the output power to the value speci-
fied.
20.4.3 Electrical equipment cubicle
COMPACT Air:
One 2-pole 3A Automatic circuit breaker for 230V control
current
COMPACT Heat:
One 2-pole 3A Automatic circuit breaker for 230V control
current
One 2-pole 10A Automatic circuit breaker for control cur-
rent to fans
20.4.4 Heat Exchanger Motor
COMPACT Air and COMPACT Heat:
Stepping motor, 3-phase, 5.8 A (2A)*, 62 V max 90 V.
*) The motor controls limit the output power to the value speci-
fied.
20.4.5 Control Inaccuracy
Temperature ± 1
o
C.
Airflow ± 5%.