9.2.8 External Temperature Sensors
An external room sensor and external outdoor sensor can
be connected to the IQnomic control unit. The sensor can
be used when the internal sensor of the unit does not
provide representative values.
External Extract air/Room can measure the extract air
temperature in a larger room instead of the temperature
inside the air handling unit.
External Outdoor measures the outdoor air temperature
outdoors, instead of the temperature inside the air han-
dling unit.
Connect the TBLZ-1-24-2 sensor by means of the modular
cable supplied, to an optional connection marked Internal
BUS 1.
Sensor TBLZ-1-24-2 can be used both as a room sensor
and an outdoor sensor. They must therefore be addressed
according to function using the function selector switch
on the sensor. The function selector switch must be in
Position 0 when the room sensor is used and in Position A
when an outdoor sensor is used.
If the TBLZ-1-24-2 sensor is installed outdoors, it must be
mounted inside an air-tight enclosure.
As an alternative, a temperature reading can be commu-
nicated to the air handling unit from a supervisory system,
for instance.
Settings:
Value
Setting range
Factory setting
External Extract air/Room Inactive//IQnomic
Communication
Inactive
External Outdoor
Inactive//IQnomic
Communication
Inactive
Alarms
0 - 9990 min.
5 min.
* Applies to COMPACT Heat
only
* TEMPERATURE *
TEMPERATURE REG
AIRING FUNCTION
SUMMER NIGHT COOL
INTERM. NIGHT HEAT
MORNING BOOST
SETPOINT TEMP DISPL
HEATING
EXT. SENSORS
*
*
*
* Applies to COMPACT Heat
only
* TEMPERATURE *
TEMPERATURE REG
AIRING FUNCTION
SUMMER NIGHT COOL
INTERM. NIGHT HEAT
MORNING BOOST
SETPOINT TEMP DISPL
HEATING
EXT. SENSORS
*
*
*
9.2.7 Heating
(applies to COMPACT Heat only)
The air handling unit is utilised for heating the room dur-
ing a preset time period. The function must be activated
manually.
The air handling unit switches over to extract air/room
regulation (control) of the temperature. The air heater, air
recirculation section and BOOSTER function are activated.
Settings:
Value
Setting range Factory set-
ting
Time for manual heating
hour:min
00:45
EA/Room Temp*
10 - 30 °C
22 °C
SA min*
8 - 20 °C
15 °C
SA max*
16 - 50 °C
28 °C
* If these values are changed, the corresponding values
under Morning BOOST will also change.