INSTALLATION
FUNCTIONS
*FUNCTIONS*
TEMPERATURE
AIR FLOW/PRESSURE
FILTER
OPERATION
HEATING
COOLING
IN/OUTPUTS
IQnomic Plus
ALL YEAR COMFORT
9.2.2 Airing Function
The airing function means that the air handling unit will
operate in the max. speed mode and temperature during
the preset period.
The function requires either a presence detector or has to
be manually activated in Main Menu 1.
9.2.2.1 Automatic Airing
The presence detector shall be connected to the external
input, selected for external high speed.
Conditions that must be met for automatic airing to start:
• Presence of occupant(s) has been indicated during at
least 10 minutes.
• Occupant(s) are no longer present and the preset time
period for high speed airflow has expired.
Conditions that must be met for automatic airing to stop:
• Airing has taken place during the preset time period.
• The presence of occupant(s) is indicated via input for
externally actuated high speed airflow.
9.2.2.2 Manual Airing
The Airing function can be started from Main Menu 1 and
will then operate during the preset time period.
The Airing function can be manually cancelled by setting
the air handling unit to Normal Operation in the control
display.
Settings:
Value
Setting range Factory set-
ting
Function, Off/On
Inactive/Active Inactive
Supply air temperature
10 - 20 °C
10 °C
Time period
10-60 min.
15 min.
* Applies to COMPACT Heat
only
* TEMPERATURE *
TEMPERATURE REG
AIRING FUNCTION
SUMMER NIGHT COOL
INTERM. NIGHT HEAT
MORNING BOOST
SETPOINT TEMP DISPL
HEATING