9.5.2 Extended Operation
The control unit’s inputs, INP. 1 (terminals 5 and 6) and
INP.2 (terminals 7 and 8) can be selected for the external
high speed and external low speed functions. They can be
used for overtime running activated by a pushbutton, for
example.
Desired time in hours and minutes can be set as follows.
The time period preset for manual high speed is applicable
to extended (overtime) operation in Main Menu 1.
Settings:
Value
Setting
Factory
range settings
External low speed
0:00 - 23:59
0:00
External high speed
0:00 - 23:59
0:05
Man. High speed
0:00 - 23:59 0:45
(hour:min) (hour:min)
9.5 Operation
9.5.1 Switch clock
Basic functions are set at INSTALLATION LEVEL and
the values are read and set at USER LEVEL.
The switch clock controls the operating times of the unit.
The following two basic functions can be set:
LOW SPEED – HIGH SPEED
Low speed is the basic level and times for high speed oper-
ation are set at USER LEVEL under SWITCH CLOCK.
STOP – LOW SPEED – HIGH SPEED
Stop is basic level and times for low speed and high speed
operation are set at USER LEVEL under SWITCH CLOCK.
Settings:
Value
Setting range
Factory settings
Function
Low speed/High speed
Low speed/High speed
Stop/Low speed/High speed
9.5.3 Summer time/Winter time
The time and date readings include factory-preset auto-
matic changeover from summer time to normal time and
vice versa, thus conforming to EU standard (the last Sun-
day in March and the last Sunday in October respectively).
This automatic changeover can be blocked and set as inac-
tive.
Settings:
Value
Setting
Factory
range settings
Summer time/Winter time
Inactive/active Active