Installation - Unit
41
[ I ]
2
nd
Room Extract
(m
3
/h)
The additional 2
nd
Room Extract module enables adjustment of max air flow of ventilation for
exhaust of the 2
nd
room. Diameter, length and number of turns in the ducting as well as air inlet
size limit the air stream (see table above):
•
off: No exhaust ducting installed or extract opening blocked
•
30: One flex-duct connected (with extract valve
125)
•
60: Two flex-ducts installed (with extract valve
125 and completely open)
• 100: Three flex-ducts or spiral-seam pipe DN100 installed (with extract valve
200)
Note
Incorrect adjustment or high air friction coefficient will lead to higher noise level and premature
filter error warning.
Summer Cooling
(°C)
A special feature of your freeAir 100 is the active summer cooling. In the warm season the
device automatically activates a bypass in order to (mostly at night) cool down rooms with fresh
outside air. The amount of air will be increased, if necessary.
Select your desired temperature for the supply air room.
Room Area
(m
2
)
Enter here the number of square meters to be ventilated. Please factor in all connected rooms.
This input is the basis for minimum ventilation calculations.
Notes
• If you find the intermittent operation bothersome, adjust the room area
to 60 m
2
or 75 m
2
.
• Adjust the Room Area to 60 or 75 m
2
to guaranty a level of minimum ventilation of 20 m
3
/h
for humidity control according to DIN 1946-6.
• Higher minimum ventilation of 40 m³/h or 60 m³/h you can have by: 2 DIP switches up and
the right one down, or all up (2
nd
Room Extract must not be set to 30 m³/h).
Summary of Contents for bluMartin freeAir 100
Page 1: ...Manual G General O Operation I Installation S Service ...
Page 20: ...Installation Bare Brickwork Set 18 I Drawings ...
Page 21: ...Installation Bare Brickwork Set 19 I ...
Page 23: ...Installation Bare Brickwork Set 21 I ...
Page 24: ...Installation Bare Brickwork Set 22 I ...
Page 25: ...Installation Bare Brickwork Set 23 I ...
Page 26: ...Installation Bare Brickwork Set 24 I ...
Page 27: ...Installation Bare Brickwork Set 25 I ...
Page 28: ...Installation Bare Brickwork Set 26 I ...
Page 59: ...Service S 57 For troubleshooting visit the website www bluMartin de freeair support ...