50
A-96.250.331 / 230320
AMU Powercon
Program List and Explanations
Parameter Conductivity:
5.2.1.40.10
Range low: 0
S–300 mS
5.2.1.40.20
Range high: 0
S–300 mS
Parameter Temperature
5.2.1.40.11
Range low: -25 to +270 °C
5.2.1.40.21
Range high: -25 to +270 °C
Parameter Sample flow
5.2.1.40.12
Range low: 0–50 l/h
5.2.1.40.22
Range high: 0–50 l/h
Parameter Cond. uc:
5.2.1.40.13
Range low: 0
S–300 mS
5.2.1.40.23
Range high: 0
S–300 mS
As control
output
Signal outputs can be used for driving control units. We distinguish
different kinds of controls:
P-controller:
The controller action is proportional to the devia
-
tion from the setpoint. The controller is characterized by the
P-Band. In the steady-state, the setpoint will never be
reached. The deviation is called steady-state error.
Parameters: setpoint, P-Band
PI-controller:
The combination of a P-controller with an
I-controller will minimize the steady-state error. If the reset
time is set to zero, the I-controller is switched off.
Parameters: setpoint, P-Band, reset time.
PD-controller:
The combination of a P-controller with a
D-controller will minimize the response time to a fast change
of the process value. If the derivative time is set to zero, the
D-controller is switched off.
Parameters: setpoint, P-Band, derivative time.
PID-controller:
The combination of a P-, an I- and a D-control
-
ler allows a proper control of the process.
Parameters: setpoint, P-Band, reset time, derivative time.
Ziegler-Nichols method for the optimization of a PID controller:
Parameters
: Setpoint, P-Band, Reset time, Derivative time