20
A-96.250.331 / 230320
AMU Powercon
Installation
2.12. Relay Contacts
2.12.1 Alarm Relay
NOTICE:
Max. load 100 mA/50 V
Alarm output for system errors. Error codes see
.
2.12.2 Relay 1 and 2
NOTICE:
Max. load 100 mA/50 V
Relay 1: Terminals 1/2
Relay 2: Terminals 3/4
Program List and Explanations, p. 44
, Menu
Installation
2.13. Signal Output 1 and 2 (current outputs)
NOTICE:
Max. burden 510 Ω
If signals are sent to two different receivers, use signal isolator
(loop isolator).
Signal output 1: Terminals 13 (+) and 12 (-)
Signal output 2: Terminals 14 (+) and 12 (-)
Program List and Explanations, p. 44
, Menu
Installation
Terminals Description
NC
a)
Normally
Closed
a) As defined when ordering
5/6
Active (opened) during normal
operation.
Inactive (closed) on error and loss of
power.
NO
a)
Normally
Open
5/6
Active (closed) during normal
operation.
Inactive (opened) on error and loss of
power.