66
Parameter
Range
Default
Description
Target Value
0~60000
5000
Set value = 0: The feeding system will not work.
SP1 Lead Value
[High-speed Feed]
0~60000
1000
Set value = 0: The DO switch ‘High-speed Feed’ will not
participate in the feeding process.
Set value > 0: When ‘Feeding Weight
≥
(Target Value
-
SP1
Lead)’ in the feeding process, the DO switch ‘High-speed Feed’
will turn off automatically.
The auto-feeding process of the first batch after ‘Start’ signal
inputted:
If ‘Weight
≥
(Target Value – SP3 Fall)’, then the auto-feeding
process of the first batch will be skipped.
If ‘(Target Value × 50%)
≤
Weight
≤
(Target Value – SP3
Fall)’, then the DO switches ‘Low-speed Feed’ and
‘Medium-speed Feed’ will not participate in the auto-feeding
process of the first batch, and only the DO switch ‘Low-speed
Feed’ will do.
SP2 Lead Value
[Medium-speed Feed]
0~60000
100
Set value = 0: The DO switch ‘Medium-speed Feed’ will not
participate in the feeding process.
Set value > 0: When ‘Feeding Weight
≥
(Target Value
-
SP2
Lead)’ in the feeding process, the DO switch ‘Medium-speed
Feed’ will turn off automatically.
SP3 Fall Value
[Low-speed Feed]
0~60000
50
When ‘Feeding Weight
≥
(Target Value
-
SP3 Fall)’ in the
feeding process, the DO switch ‘Low-speed Feed’ will turn off
automatically.
Note: It has one more decimal than ‘Target Value’.
Allowed Positive
Deviation
0~60000
5
Positive Deviation = Final Feeding Weight
–
Target Value.
If ‘Positive Deviation > Allowed Value’, the DO switch ‘Positive
Deviation Alarm’ will turn on automatically.
Allowed Negative
Deviation
0~60000
5
Negative Deviation = Target Value
–
Final Feeding Weight.
If ‘Negative Deviation > Allowed Value’, the DO switch
‘Negative Deviation Alarm’ will turn on automatically.
Non-load Zero Range
0~60000
0
Set value = 0: In the auto-Dumping process, the condition
‘Weight
≤
Non-load Zero Range’ will be ignored.
Set value > 0: In the auto-Dumping process, ‘Weight
≤
Non-load
Zero Range’ will be used as the judging condition that the
materials in the weighing hopper have been dumped completely.
Weight Upper Limit
0~999999
0
Set value = 0: No judging ‘Weight Upper Limit’.
Set value > 0: If ‘Weight
≥
Upper Limit’, the controller will
display alarm message.
Boost Delay
0.00~9.99
0.00
Delay Time to Boost Material After SP1 High-speed Feeding [s]
Boost Time
0.00~9.99
0.00
Max. Material Boosting Time After SP1 High-speed Feeding [s]
High Feed AO
0.00~10.00
5.00
High-speed Feeding AO Control Voltage [V]
Med. Feed AO
0.00~10.00
3.00
Medium-speed Feeding AO Control Voltage [V]
Low Feed AO
0.00~10.00
2.00
Low-speed Feeding AO Control Voltage [V]
Feeder High AO
0.00~10.00
5.00
Meterial Feeder High-speed AO Control Voltage [V]
Feeder Medium AO
0.00~10.00
3.00
Meterial Feeder Medium-speed AO Control Voltage [V]
Feeder Low AO
0.00~10.00
2.00
Meterial Feeder Low-speed AO Control Voltage [V]
Material-supply AO
0.00~10.00
5.00
Material Supplying AO Control Voltage [V]
Product-convey AO
0.00~10.00
5.00
Product conveying AO Control Voltage [V]