41
6.3.6 Communication Parameters
No.
Sign
Range
Default
Description
REG
800
Communication
Address
0~99
1
Communication Address
40801
801
802
COM1 Baud Rate
COM2 Baud Rate
0~2
0
0
COM1[RS232]/COM2[RS485] Baud Rate
0
:
9600bps; 1
:
19200bps; 2: 115200bps
40803
40805
803
804
COM1 Parity
Check
COM2 Parity
Check
0~2
0
0
COM1/COM2 Parity Check
0. None
1. Even
2. Odd
40807
40809
805
806
COM1 Comm.
Mode
COM2 Comm.
Mode
0~3
0
3
COM1/COM2 Communication Mode
0: Host-salve Modbus[ASCII]
1: Host-salve Modbus[RTU]
2: Continuous Sending[ASCII]
3: EMR-AO08-U/0-10V[RTU]
40811
40813
807
Continuous
Sending
0~7
1
Data for Continuous Sending Mode
0: Real-time Weight
1: Final Feeding Weight
2: Batch Count
3: Totalized Weight
4: All Above Data
40815
808
Continuous
Sending Frequency
0~7
2
Continuous Sending Frequency
[Hz]
0: 1Hz; 1: 2Hz; 2: 5Hz; 3: 10Hz
4: 20Hz; 5: 25Hz; 6: 50Hz; 7: 100Hz
40817
Note
Baud Rate
Max. Sending Frequency
9600 bps
50Hz
19200 bps
100Hz
115200 bps
100Hz
809
810
COM1 Modbus
Data Format
COM2 Modbus
Data Format
0~3
0
COM1/COM2 Modbus Data Format
Reading&Writing Order of 4-Byte Registers:
0: H4 H3 L2 L1
1: H3 H4 L1 L2
2: L1 L2 H3 H4
3: L2 L1 H4 H3
The HEX byte order of float and long int
registers in the controller is ‘H4 H3 L2 L1’.
40819