32
No.
Sign
Range
Default
Description
REG
307
t2 SP3 OFF
Holding Time
0.03
~9.99
0.50
t2 SP3 OFF Holding Time
[s]
Used for SP3 Inching Feeding Mode.
40315
308
SP3 Re-feed for
Fall Point
0~1
0
Auto SP3 Re-feed for Fall Point
0: OFF
1: ON
[If the auto-feeding process stops
abnormally because of heavy impact on the
weighing hopper, and ‘Feeding Weight < (Target
Value
-
SP3 Fall)’, the DO switch ‘SP3
Low-speed Feed’ will turn on again automatically
for re-feeding. When ‘Feeding Weight
≥
(Target
Value
-
SP3 Fall)’, the DO switch ‘SP3
Low-speed Feed’ will turn off automatically to stop
re-feeding]
40317
309
t3 Re-feeding
Time for Neg.
Dev.
0.00
~5.00
0.00
t3 Re-feeding Time for Negative Deviation
[s]
Set value = 0: No Auto Re-feeding.
Set value > 0: After the processes of auto-feeding
and ‘Auto SP3 Re-feed for Fall Point’ stopped, if
‘Feeding Weight < (Target Value
-
Allowed
Negative Deviation)’, the process of ‘Auto SP3
Re-feed for Negative Deviation’ with t3 as the
re-feeding time per time will start automatically,
once ‘Feeding Weight
≥
(Target Value
-
Allowed
Negative Deviation)’ or the re-feeding times
reached to 10, the re-feeding process will stop
immediately. Empirical value: t3 = 0.10~0.20s.
40319
310
Auto Pause for
Deviation Alarm
0~1
0
Auto Pause for Deviation Alarm
0: OFF
1: ON
[The controller will display alarm
message in Pause state. In Pause state with
Negative Deviation Alarm, it’s allowed to do
‘Manual SP3 Re-feed’, when ‘Feeding Weight
≥
(Target Value
-
Allowed Negative Deviation)’, the
re-feeding process will stop automatically, and then
press the DI button ‘Start/Clear Alarm’ to recover
running]
40321
311
Fall Value Auto
Correction
0~1
0
Fall Value Auto Correction
0: OFF
1: ON
40323