38
No.
Sign
Range
Default
Description
REG
407
T6 Max.
DumpGate
Opening Time
0.00
~9.99
0.50
T6 Max. Dumping Gate Opening Time
[s]
In the dumping process, once the dumping gate’s
opening time is up to T6 or the DI switch ‘Dumping
Gate Opened in Place’ turns on, the process of
opening dumping gate will end.
With the DI signal ‘Dumping Gate Opened in Place’
being used, if the DI doesn’t turn on after the
opening time has been up to T6, the alarm signal
‘Dumping Gate Unopened’ will be outputted, and
the auto-running process will pause. After fault
handling, press DI button ‘Start / Clear Alarm’ to
recover running.
40415
408
T7 Delay to
Close Dumping
Gate
0.00
~9.99
0.50
T7 Delay to Close Dumping Gate
[s]
If Parameter [202] ‘Non-load Zero Range’ = 0:
After the dumping gate opened, the condition
‘Weight
≤
Non-load Zero Range’ will be ignored,
after the time T7 delayed for ensuring all of the
materials in the weighing hopper dumped
completely, the dumping gate will be closed
automatically.
If Parameter [202] ‘Non-load Zero Range’ > 0:
After the dumping gate opened, only when ‘Weight
≤
Non-load Zero Range’ and then the time T7
delayed for ensuring all of the materials in the
weighing hopper dumped completely, the dumping
gate will be closed automatically.
In the meantime, the Bag-shaking process will start
if it is allowed by setting parameter [320~325], and
the ‘Bag-releasing Permission Timer’ will start
timing.
40417