3 1/2 in. 

(89 mm)

6 in.

(152 mm)

 

Top View of 

Fireplace

 

45

o

Combustible materials may 

project  beyond  either side 

of  the  fireplace  opening 

as  long  as  they  are  kept 

within  the  shaded  area 

illustrated  here.

Combustible Materials 

Allowed In Shaded Area 

“Safe Zone”

Combustible Walls 

shown in dark gray

At 6 in. minimum 

side wall clearance, 

a combustible wall 

can project to any 

length.

9

NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.

SUPERIOR

®

  •  DIRECT-VENT GAS FIREPLACES (SDV35-N-2)  •  INSTALLATION INSTRUCTIONS

Figure 8: Minimum Mantel Clearances

12 (305) MANTEL

10 (254) MANTEL

8 (203) MANTEL

6 (152) MANTEL

4 (102) MANTEL

4

(102)

14

(356)

12

(305)

10

(254)

2 (51) MANTEL

TOP OF

APPLIANCE

6

(152)

Hood

8

(203)

MANTEL CLEARANCES

Inches (mm)

Wall Finishes / Surrounds / Mantels

Note: Combustible wall finish materials and/or surround materials must not be allowed to encroach the area defined by the appliance front face (black 

sheet metal). Never allow combustible materials to be positioned in front of or overlapping the appliance face.

Non-combustible materials, such as surrounds and other appliance trim, may be installed on the appliance face with these exceptions: they must not 

cover any portion of the removable glass panel or control compartment.

Vertical installation clearances to combustible mantels vary according to the depth of the mantel. See 

Figure 8

. Mantels constructed of 

non-combustible materials may be installed at any height above the appliance opening; however, do not allow anything to hang below the 

fireplace hood.

Minimum clearance requirements include any projections such as shelves, window sills, mantels, etc. above the appliance.

NOTE:

 We recommend the use of high temperature paint (rated 175 °F, or higher) on the underside of the mantel.

Figure 9: 

Minimum Distance to Side Wall

f i r e - p a r t s . c o m

Summary of Contents for SDV35-2

Page 1: ...xactly a fire or explosion may result causing property damage personal injury or death HOT GLASS WILL CAUSE BURNS DO NOT TOUCH GLASS UNTIL COOLED NEVER ALLOW CHILDREN TO TOUCH GLASS UNE SURFACE VITR E...

Page 2: ...paring Appliance Vent Collar 13 Step 4 Installing Vent System 13 Vertical Termination Systems 14 Vent Section Length Chart 14 Vertical Vent Tables and Figures 17 Horizontal Termination System 19 Horiz...

Page 3: ...sed in the installation of this appliance Seules les trousses de garniture fournies par le fabricant doivent tre utilis es pour l installation de cet appareil This appliance complies with National Saf...

Page 4: ...OVINCIAL OR TERRITORIAL AUTHORITIES HAVING JURISDICTION AND IN ACCORDANCE WITH THE REQUIREMENTS OF THE CAN CGA B149 1 OR CAN CGA B149 2 INSTALLATION CODES REQUIREMENTS FOR THE COMMONWEALTHOFMASSACHUSE...

Page 5: ...om It is especially important to insulate outside chase cavity between studs and under floor on which appliance rests if floor is above ground level Gas line holes and other openings should be caulked...

Page 6: ...ion Storm Collar Concentric Vent Pipe Flashing 1 inch 25 4 mm Minimum Clearance to Combustibles Figure 4 Termination Heights for Vents Above Flat or Sloped Roofs Vertical Vent Termination Clearances T...

Page 7: ...c e m n o n o t e c n a r a e l C J e c n a i l p p a r e h t o y n a o t t e l n i r i a n o i t s u b m o c e h t s e c n a i l p p a r o f m c 5 1 s e h c n i 6 m c 0 3 s e h c n i 2 1 W k 3 h u t...

Page 8: ...minimize obstructions to the space above the appliance Do not insulate the space between the appliance and the area above it see Figure 7 The minimum height from the base of the appliance to the unde...

Page 9: ...materials must not be allowed to encroach the area defined by the appliance front face black sheet metal Never allow combustible materials to be positioned in front of or overlapping the appliance fa...

Page 10: ...EMPT from the 1 2 in clearance to combustible requirements for the firebox outer wrapper Combustible framing may be in direct contact with the nailing flanges and may be located closer than 1 2 in fro...

Page 11: ...51 Right Side View 14 43 1092 12 7 16 9 16 316 Inches Millimeters 5 29 1 2 749 19 406 35 1 8 892 37 5 32 944 Overall unit height Note J box can be relocated in either the right front or left front cor...

Page 12: ...ition Canada Step 2 ROUTING GAS LINE Route a 1 2 in 13 mm gas line to the left side of the appliance as shown in Figure 14 Gas lines must be routed constructed and made of materials that are in strict...

Page 13: ...USA or the current standards of CAN CGA B149 1 in Canada Ensure clearances are in accordance with local installation codes and the requirements of the gas supplier D gagement conforme aux codes d inst...

Page 14: ...1 0 1 0 5 0 6 6 8 1 5 5 1 0 0 0 0 4 4 5 0 9 1 5 7 8 5 1 1 0 0 0 4 5 5 6 9 1 5 7 3 6 1 0 1 0 0 4 5 5 5 0 2 5 2 1 7 1 0 1 1 5 0 7 7 0 2 5 2 7 1 0 0 0 6 0 6 5 1 1 2 5 2 6 7 1 1 0 0 6 0 7 5 7 1 2 5 2 1 8...

Page 15: ...h 3 pilot holes Slip the plain end over the locking channel end of a standard SV4 5 vent component the required distance and secure with three screws Maintain a minimum 1 in 25 mm clearance to combust...

Page 16: ...he required clearances to combustibles 1 in 25 mm at all sides for all vertical runs and 3 in 76 mm at the top 1 in 25 mm at sides and 1 in 25 mm at the bottom for all horizontal inclined runs H Frame...

Page 17: ...Spacer SF4 5VF Ceiling Firestop Spacer SV4 5VF Figure 30 Rear Vent ONE 90 DEGREE ELBOW This table shows a 1 V to 2 H ratio For every 1 foot of V vertical you are allowed 2 feet of H horizontal run up...

Page 18: ...feet 6 096 m Max V V1 H H1 40 ft 12 192 m Max meters meters Example If 20 feet of H horizontal vent run is needed then 4 feet minimum of V vertical vent will be required This table shows a 1 V to 5 H...

Page 19: ...outer pipe elements with the same procedure Sealant and securing screws are not required Note An elbow may also be attached to the appliance collar Attach in the same manner as you would a vent secti...

Page 20: ...ll or siding by more than the 1 1 4 in 32 mm as shown in Figure 36 SVHRK Snorkel Cap The snorkel cap is designed to be fitted into a basement window box The SVHRK cap is for use with flex vent The ver...

Page 21: ...ing SV4 5HT 2 termination kit HORIZONTAL VENT FIGURES TABLES Note Two 45 degree elbows may be used in place of one 90 degree elbow The same rise to run ratios as shown in the venting figures for 90 el...

Page 22: ...then 4 feet minimum of V vertical vent will be required This table shows a 1 V to 5 H ratio For every 1 foot of V vertical you are allowed 5 feet of H horizontal run up to a maximum horizontal run of...

Page 23: ...5 1 524 Elbow Only 5 1 524 1 0 305 10 3 048 2 0 610 15 4 572 3 0 914 20 6 096 4 1 219 meters TABLE L meters H Maximum 1 1 H H1 20 feet 6 096 m Max V V H H 40 ft 12 192 m Max Example If 20 feet of H h...

Page 24: ...inner adaptor collar approximately 1 2 inch from the end 3 Pull and extend the inner flexible vent pipe 4 Slide the inner flex pipe over the adaptor collar Ensure the flexible vent pipe completely eng...

Page 25: ...The gas valve is set in place and pre wired at the factory on both models Wiring see Figure 46 This unit is not provided with factory installed controls therefore one of the optional control switches...

Page 26: ...oor by sliding the hinge pin located at the door s left side to the right until it disengages from the left corner post hole Pull the door diagonally to the left away from the fireplace The control va...

Page 27: ...e pipes fittings can result in corrosion over time A Light the appliance refer to the lighting instructions label in the control compartment or in the Care and Operation Instructions manual B Brush al...

Page 28: ...e logs until the appliance installa tion has been completed the gas lineconnectedandtestedforleaks and the initial burner operation has been checked out Thesizeandpositionofthelogset was engineered to...

Page 29: ...wn Position the rear log on the brackets at the rear of the firebox with the log s notches directly over the brackets Position the right log log no 3 by inserting the pin from the rear log into the ho...

Page 30: ...is provided to aid you in achieving the correct air shutter adjustment for your installation Figure 54 Door Removal Removing the Glass Enclosure Panel see Figure 54 Remove the top radiant panel To acc...

Page 31: ...gures 65 and 66 All models must have hoods installed prior to operating Slide the hood into the slots on the lower edge of the radiant panel Figure 57 FINISHING REQUIREMENTS Wall Details Complete fini...

Page 32: ...raisse ou d huile Collez l tiquette sur la surface de la plaque de l interrupteur mural qui contr le le foyer Figure A ou du thermostat mural Figure B Choisissez la langue qui est principalement parl...

Page 33: ...246 SV4 5HF 10 Firestop Spacer Hori zontal rigid 3 1 1 spac ing 10 Pack H2247 SV4 5VF 10 Firestop Spacer Verti cal rigid 1 1 1 spac ing 10 Pack 96K92 SV4 5SP Support Plate INSTALLATION ACCESSORIES Lis...

Page 34: ...Small Square Termination for flex without flex vent Ref Instr 750204M INSTALLATION ACCESSORIES CONTINUED All compressed flex vents can be expanded up to two times Listed Secure Flex Components Cat Mod...

Page 35: ...the appliance see Page 30 WARNING This conversion kit shall be installed by a qualified service agency in accordance with the manufacturer s instructions and all applicable codes andrequirementsofthea...

Page 36: ...crews as shown in Figure 59 Tighten the screws to 25 in lb Step 8 Install the enclosed identification label to the valve body where it can be easily seen Step 9 Refer to Figure 60 and replace the pilo...

Reviews: