22
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
SUPERIOR
®
• DIRECT-VENT GAS FIREPLACES (SDV35-N-2) • INSTALLATION INSTRUCTIONS
TABLE H
H+H
1
Maximum
H Maximum
V Minimum
feet
feet
feet
5
(1.524)
2
(0.610)
1
(0.305)
10
(3.048)
4
(1.219)
2
(0.610)
15
(4.572)
6
(1.829)
3
(0.914)
20
(6.096)
8
(2.438)
4
(1.219)
V + H + H1 = 40 feet (12.2 m) Max.
H = 8 feet (2.438 meters) Max.
H + H1 = 20 feet (6.096 meters) Max.
(meters)
(meters)
(meters)
H
+ H
1
Maximum
V Minimum
feet
feet
3
(0.914)
Elbow Only
5
(1.524)
1
(0.305)
10
(3.048)
2
(0.610)
15
(4.572)
3
(0.914)
20
(6.096)
4
(1.219)
V +
H
+ H
1
= 40 feet (12.2 m) Max.
H
+ H
1
= 20 ft. (6.096 m) Max.
TABLE J
(meters)
(meters)
HORIZONTAL VENT FIGURES/TABLES (continued)
Figure 40:
Rear Vent—TWO 90-DEGREE ELBOWS
Figure 41:
Top Vent—TWO 90-DEGREE ELBOWS
Square termination (SV4.5HT-2) shown.
See Table 9 on Page 21 as an aid in venting component selection for a particular range
of exterior wall thicknesses.
Note: Install the U-shaped vent restrictor in any vent run with more than 8 ft of vertical
rise (See
Page 13
).
Square termination (SV4.5HT-2) shown.
Example: If 20 feet of (H) horizontal vent run is needed, then 4
feet minimum of (V) vertical vent will be required.
This table shows a 1 (V) to 5 (H) ratio. For every 1 foot of (V)
vertical, you are allowed 5 feet of (H) horizontal run, up to a
maximum horizontal run of 20 feet.
See Table 9 on Page 21 as an aid in venting component
selection for a particular range of exterior wall thicknesses.
Note: Install the U-shaped vent restrictor in any vent run with
more than 8 ft of vertical rise (See
Page 13
).
Example: If 20 feet of (H) horizontal vent run is
needed, then 4 feet minimum of (V) vertical vent
will be required.
This table shows a 1 (V) to 5 (H) ratio. For every
1 foot of (V) vertical, you are allowed 5 feet of (H)
horizontal run, up to a maximum horizontal run of
20 feet.
An elbow is acceptable as 1 foot of vertical
rise except where an elbow is the only vertical
component in the system. See
Figure 38
.
V
H
H1
Ceiling Firestop/Spacer
SV4.5VF*
Wall Firestop/Spacer
SV4.5HF**
*
When using
Secure Flex
, use
Ceiling Firestop/Spacer
SF4.5VF
.
**
When using
Secure Flex
, use
Wall Firestop/Spacer
SF4.5HF
.
Wall Firestop/Spacer
SV4.5HF**
H1
V
H
Ceiling
Firestop/Spacer
SV4.5VF*
Wall Firestop/
Spacer
SV4.5HF**
*
When using
Secure Flex
, use
Ceiling Firestop/Spacer
SF4.5VF
.
**
When using
Secure Flex
, use
Wall Firestop/Spacer
SF4.5HF
.
®
f i r e - p a r t s . c o m