  •  DIRECT-VENT GAS FIREPLACES (SDV35-N-2)  •  INSTALLATION INSTRUCTIONS

       WARNING 

I m p r o p e r   i n s t a l l a t i o n , 

adjustment, alteration, service 

or maintenance can cause injury 

or property damage. Refer to 

this manual. For assistance or 

additional information consult 

a qualified installer, service 

agency or the gas supplier.

       WARNING 

Failure to comply with these 

installation instructions will 

result in an improperly installed 

and operating appliance, voiding 

its warranty. Any change to this 

appliance and/or its operating 

controls is dangerous.

       WARNING 

Clothing or other flammable 

material should not be placed 

on or near the appliance.

       AVERTISSEMENT 

On ne devrait pas placer de 

vêtements ni d’autres matières 

inflammables sur l’appareil ni à 

proximité.

       WARNING 

Any safety screen or guard 

removed for servicing the 

appliance must be replaced 

prior to operating the appliance.

       AVERTISSEMENT 

Tout écran ou protecteur retiré 

pour permettre l’entretien de 

l’appareil doit être remis en 

place avant de mettre l’appareil 

en marche.

Note: Installation and repair should be 

done by a qualified service person. The 

appliance should be inspected before use 

and at least annually by a professional 

service person. More frequent cleaning 

may be required due to excessive lint from 

carpeting, bedding material, etcetera. It 

is imperative that control compartments, 

burners and circulating air passageways of 

the appliance be kept clean.

Remarque: L’installation et la 

réparation devrait être confiées à un 

technicien qualifié. L’appareil devrait 

faire l’objet d’une inspection par un 

technicien professionnel avant d’être 

utilisé et au moins une fois l’an par la 

suite. Des nettoyages plus fréquents 

peuvent être nécessaires si les tapis, 

la literie, et cetera produisent une 

quantité importante de pous-sière. Il 

est essentiel que les compartiments 

abritant les commandes, les brûleurs 

et les conduits de circulation d’air de 

l’appareil soient tenus propres.

Do not use these appliances if any part 

has been under water. Immediately 

call a qualified, professional service 

technician to inspect the appliance 

and to replace any parts of the control 

system and any gas control which have 

been under water.

Ne pas utiliser cet appareil s’il a été 

plongé, même partiellement, dans 

l’eau. Appeler un technicien qualifié 

pour inspecter l’appareil et remplacer 

toute partie du système de commande 

et toute commande qui a été plongée 

dans l’eau.

Only trim kit(s) supplied by the 

manufacturer shall be used in the 

installation of this appliance.

Seules les trousses de garniture 

fournies par le fabricant doivent être 

utilisées pour l’installation de cet 

appareil.

This appliance complies with National 

Safety Standards and is tested and listed 

by OMNI-Test Laboratories, Inc. (Report 

No. 116-F-13g-5) to ANSI Z21.88-2009 (in 

Canada, CSA-2.33-2009), and CAN/CGA-

2.17-M91(R2009) in both USA and Canada, 

as a vented gas fireplace heater.

This appliance is listed by OMNI-Test 

Laboratories for installation in bedrooms 

and Manufactured Homes. 
Misc. Codes / Standards 

The Installation must conform to local codes 

or, in the absence of local codes, with the 

National Fuel Gas Code, ANSI Z223.1—latest 

edition / NFPA 54—latest edition (In Canada, 

the current CAN/CGA-B149.1 installation 

code).The appliance, when installed, must be 

electrically grounded and wired in accordance 

with local codes or, in the absence of local 

codes, with the National Electrical Code, 

ANSI/NFPA 70—latest edition, or the 

Canadian Electrical Code, CSA C22.1—

latest edition.
Provide adequate clearances around 

air openings and adequate accessibility 

clearance for service and proper operation. 

Never obstruct the front or back openings of 

the appliance.

These appliances are designed to operate 

on natural or propane gas only. The use 

of other fuels or combination of fuels will 

degrade the performance of this system and 

may be dangerous.

This fireplace is designed as a supplemental 

heater. Therefore, it is advisable to have an 

alternate primary heat source when installed in 

a dwelling.
This appliance must not be connected to a 

chimney or flue serving a separate solid fuel 

burning appliance.
This system can be operated during a power 

outage, and feature manually operated  

HI/LO flame control. The BTU Input for this 

appliance is shown in 

Table 1.

All units are assembled for use with natural 

gas. A propane conversion kit is provided 

with this appliance. See Gas Conversion Kits 

on 

Page 35

 for installation instructions. 

Models

Input Rate (BTU/HR)

Nat. Gas

Prop. Gas

SDV35-2

20,000 high

12,800 low

20,000 high

15,200 low

Table 1: Input (BTU/HR) Gas Valves

       WARNING 

Improper installation or use of 

this appliance can cause serious 

injury or death from fire, burns, 

explosion or carbon monoxide 

poisoning.

       WARNING 

Failure to position the parts in 

accordance with these diagrams 

or failure to use only parts 

specifically approved with this 

appliance may result in property 

damage or personal injury.

       AVERTISSEMENT 

Risque de dommages ou de 

blessures si les pièces ne sont 

pas installées conformément à 

ces schémas et ou si des pièces 

autres que celles spécifiquement 

approuvées avec cet appareil sont 

utilisées.

f i r e - p a r t s . c o m

Summary of Contents for SDV35-2

Page 1: ...xactly a fire or explosion may result causing property damage personal injury or death HOT GLASS WILL CAUSE BURNS DO NOT TOUCH GLASS UNTIL COOLED NEVER ALLOW CHILDREN TO TOUCH GLASS UNE SURFACE VITR E...

Page 2: ...paring Appliance Vent Collar 13 Step 4 Installing Vent System 13 Vertical Termination Systems 14 Vent Section Length Chart 14 Vertical Vent Tables and Figures 17 Horizontal Termination System 19 Horiz...

Page 3: ...sed in the installation of this appliance Seules les trousses de garniture fournies par le fabricant doivent tre utilis es pour l installation de cet appareil This appliance complies with National Saf...

Page 4: ...OVINCIAL OR TERRITORIAL AUTHORITIES HAVING JURISDICTION AND IN ACCORDANCE WITH THE REQUIREMENTS OF THE CAN CGA B149 1 OR CAN CGA B149 2 INSTALLATION CODES REQUIREMENTS FOR THE COMMONWEALTHOFMASSACHUSE...

Page 5: ...om It is especially important to insulate outside chase cavity between studs and under floor on which appliance rests if floor is above ground level Gas line holes and other openings should be caulked...

Page 6: ...ion Storm Collar Concentric Vent Pipe Flashing 1 inch 25 4 mm Minimum Clearance to Combustibles Figure 4 Termination Heights for Vents Above Flat or Sloped Roofs Vertical Vent Termination Clearances T...

Page 7: ...c e m n o n o t e c n a r a e l C J e c n a i l p p a r e h t o y n a o t t e l n i r i a n o i t s u b m o c e h t s e c n a i l p p a r o f m c 5 1 s e h c n i 6 m c 0 3 s e h c n i 2 1 W k 3 h u t...

Page 8: ...minimize obstructions to the space above the appliance Do not insulate the space between the appliance and the area above it see Figure 7 The minimum height from the base of the appliance to the unde...

Page 9: ...materials must not be allowed to encroach the area defined by the appliance front face black sheet metal Never allow combustible materials to be positioned in front of or overlapping the appliance fa...

Page 10: ...EMPT from the 1 2 in clearance to combustible requirements for the firebox outer wrapper Combustible framing may be in direct contact with the nailing flanges and may be located closer than 1 2 in fro...

Page 11: ...51 Right Side View 14 43 1092 12 7 16 9 16 316 Inches Millimeters 5 29 1 2 749 19 406 35 1 8 892 37 5 32 944 Overall unit height Note J box can be relocated in either the right front or left front cor...

Page 12: ...ition Canada Step 2 ROUTING GAS LINE Route a 1 2 in 13 mm gas line to the left side of the appliance as shown in Figure 14 Gas lines must be routed constructed and made of materials that are in strict...

Page 13: ...USA or the current standards of CAN CGA B149 1 in Canada Ensure clearances are in accordance with local installation codes and the requirements of the gas supplier D gagement conforme aux codes d inst...

Page 14: ...1 0 1 0 5 0 6 6 8 1 5 5 1 0 0 0 0 4 4 5 0 9 1 5 7 8 5 1 1 0 0 0 4 5 5 6 9 1 5 7 3 6 1 0 1 0 0 4 5 5 5 0 2 5 2 1 7 1 0 1 1 5 0 7 7 0 2 5 2 7 1 0 0 0 6 0 6 5 1 1 2 5 2 6 7 1 1 0 0 6 0 7 5 7 1 2 5 2 1 8...

Page 15: ...h 3 pilot holes Slip the plain end over the locking channel end of a standard SV4 5 vent component the required distance and secure with three screws Maintain a minimum 1 in 25 mm clearance to combust...

Page 16: ...he required clearances to combustibles 1 in 25 mm at all sides for all vertical runs and 3 in 76 mm at the top 1 in 25 mm at sides and 1 in 25 mm at the bottom for all horizontal inclined runs H Frame...

Page 17: ...Spacer SF4 5VF Ceiling Firestop Spacer SV4 5VF Figure 30 Rear Vent ONE 90 DEGREE ELBOW This table shows a 1 V to 2 H ratio For every 1 foot of V vertical you are allowed 2 feet of H horizontal run up...

Page 18: ...feet 6 096 m Max V V1 H H1 40 ft 12 192 m Max meters meters Example If 20 feet of H horizontal vent run is needed then 4 feet minimum of V vertical vent will be required This table shows a 1 V to 5 H...

Page 19: ...outer pipe elements with the same procedure Sealant and securing screws are not required Note An elbow may also be attached to the appliance collar Attach in the same manner as you would a vent secti...

Page 20: ...ll or siding by more than the 1 1 4 in 32 mm as shown in Figure 36 SVHRK Snorkel Cap The snorkel cap is designed to be fitted into a basement window box The SVHRK cap is for use with flex vent The ver...

Page 21: ...ing SV4 5HT 2 termination kit HORIZONTAL VENT FIGURES TABLES Note Two 45 degree elbows may be used in place of one 90 degree elbow The same rise to run ratios as shown in the venting figures for 90 el...

Page 22: ...then 4 feet minimum of V vertical vent will be required This table shows a 1 V to 5 H ratio For every 1 foot of V vertical you are allowed 5 feet of H horizontal run up to a maximum horizontal run of...

Page 23: ...5 1 524 Elbow Only 5 1 524 1 0 305 10 3 048 2 0 610 15 4 572 3 0 914 20 6 096 4 1 219 meters TABLE L meters H Maximum 1 1 H H1 20 feet 6 096 m Max V V H H 40 ft 12 192 m Max Example If 20 feet of H h...

Page 24: ...inner adaptor collar approximately 1 2 inch from the end 3 Pull and extend the inner flexible vent pipe 4 Slide the inner flex pipe over the adaptor collar Ensure the flexible vent pipe completely eng...

Page 25: ...The gas valve is set in place and pre wired at the factory on both models Wiring see Figure 46 This unit is not provided with factory installed controls therefore one of the optional control switches...

Page 26: ...oor by sliding the hinge pin located at the door s left side to the right until it disengages from the left corner post hole Pull the door diagonally to the left away from the fireplace The control va...

Page 27: ...e pipes fittings can result in corrosion over time A Light the appliance refer to the lighting instructions label in the control compartment or in the Care and Operation Instructions manual B Brush al...

Page 28: ...e logs until the appliance installa tion has been completed the gas lineconnectedandtestedforleaks and the initial burner operation has been checked out Thesizeandpositionofthelogset was engineered to...

Page 29: ...wn Position the rear log on the brackets at the rear of the firebox with the log s notches directly over the brackets Position the right log log no 3 by inserting the pin from the rear log into the ho...

Page 30: ...is provided to aid you in achieving the correct air shutter adjustment for your installation Figure 54 Door Removal Removing the Glass Enclosure Panel see Figure 54 Remove the top radiant panel To acc...

Page 31: ...gures 65 and 66 All models must have hoods installed prior to operating Slide the hood into the slots on the lower edge of the radiant panel Figure 57 FINISHING REQUIREMENTS Wall Details Complete fini...

Page 32: ...raisse ou d huile Collez l tiquette sur la surface de la plaque de l interrupteur mural qui contr le le foyer Figure A ou du thermostat mural Figure B Choisissez la langue qui est principalement parl...

Page 33: ...246 SV4 5HF 10 Firestop Spacer Hori zontal rigid 3 1 1 spac ing 10 Pack H2247 SV4 5VF 10 Firestop Spacer Verti cal rigid 1 1 1 spac ing 10 Pack 96K92 SV4 5SP Support Plate INSTALLATION ACCESSORIES Lis...

Page 34: ...Small Square Termination for flex without flex vent Ref Instr 750204M INSTALLATION ACCESSORIES CONTINUED All compressed flex vents can be expanded up to two times Listed Secure Flex Components Cat Mod...

Page 35: ...the appliance see Page 30 WARNING This conversion kit shall be installed by a qualified service agency in accordance with the manufacturer s instructions and all applicable codes andrequirementsofthea...

Page 36: ...crews as shown in Figure 59 Tighten the screws to 25 in lb Step 8 Install the enclosed identification label to the valve body where it can be easily seen Step 9 Refer to Figure 60 and replace the pilo...

Reviews: