Superior SDV35-2 Installation Instructions Manual Download Page 30

30

NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.

SUPERIOR

®

  •  DIRECT-VENT GAS FIREPLACES (SDV35-N-2)  •  INSTALLATION INSTRUCTIONS

Step 10. REMOVING AND INSTALLING 

THE GLASS DOOR 

Air Shutter Adjustment Guidelines

Amount of 

Primary Air

Flame 

Color

Air Shutter 

Adjustment

If air shutter is 

closed too far

Flame will 

be orange

Air shutter 

gap should be 

increased

If air shutter is 

open too far

Flame will 

be blue

Air shutter 

gap should be 

decreased

Step 11. BURNER ADJUSTMENTS 

Flame Appearance and Sooting

Proper flame appearance is a flame that is 

blue at the base and becomes yellowish-

orange in the body of the flame.
When the appliance is first lit, the entire 

flame may be blue and will gradually turn 

yellowish-orange during the first 15 minutes 

of operation. If the flame remains blue, or if 

the flame is orange with evidence of sooting 

(black tip), the air shutter opening may need 

to be adjusted.
If the air shutter opening is closed too far, 

sooting may develop. Sooting is indicated 

by black puffs developing at the tips of very 

long orange flames. Sooting results in black 

deposits forming on the logs, appliance 

inside surfaces and on exterior surfaces 

adjacent to the vent termination. 
Sooting is caused by incomplete combustion 

in the flames and lack of combustion air 

entering the air shutter opening. To achieve 

a warm yellowish-orange flame with an 

orange body that does not soot, the shutter 

opening must be adjusted between these two 

extremes.

Air Shutter Adjustment Guidelines

•  If there is smoke or soot present, first 

check the log set positioning to ensure 

that the flames are not impinging on 

any of the logs. If the log set is properly 

positioned and a sooting condition still 

exists, then the air shutter opening should 

be increased.

•  The more offsets in the vent system, the 

larger the air shutter opening will need 

to be.

•  An appliance operated with the air shutter 

opened too far, may have flames that 

appear blue and transparent. These weak, 

blue and transparent flames are termed 

anemic. 

•  Propane models may exhibit flames 

which candle or appear stringy. If this is 

present and persists, adjust the air shutter 

to a more closed position, then operate 

the appliance for a few more minutes to 

ensure that the flame normalizes and the 

flames do not appear sooty. 

The following chart is provided to aid you in 

achieving the correct air shutter adjustment 

for your installation.

Figure 54: Door Removal

Removing the Glass Enclosure Panel 

(see 

Figure 54

Remove the top radiant panel. To access the 

glass door securing latches, first open the 

lower control compartment door (

Figure 54

 

by pushing in simultaneously the left and 

right top corners of the door (the door is 

hinged at the bottom). 

Remove the bottom compartment door by 

sliding the hinge pin, located at the door’s left 

side, to the right until it disengages from the 

left corner post hole. Pull the door diagonally 

to the left, away from the fireplace.

Locate the two (2) latches at the top of the 

control compartment and disengage them 

from the door frame bottom vee-flange, 

pulling down on their handles to open them.

Installing the Glass Enclosure Panel 

(see 

Figure 54

Retrieve the glass door. Visually inspect the 

gasket on the backside of the frame. Gasket 

surface must be clean, free of irregularities 

and seated firmly. 

Position the door in front of the firebox 

opening with the bottom of the door held 

away from the fireplace 

(Figure 54)

. Hook the 

top flange of the door frame over the top of 

the firebox frame. 

Let the bottom of the door frame swing 

gently in towards the fireplace ensuring that 

the gasket seats evenly as the door frame 

draws shut. Fasten the two latches located 

underneath the firebox floor to the door's 

vee-flange. Close both the latches securely.

Lower Compartment Door and Hinge

Glass Door Frame

Top Flange

Glass

Door

Glass Door Latch

Firebox Floor

Glass Door Frame

Bottom Vee-flange

Only doors certified with the appliance 

shall be used.

Seules des portes certifiées pour cet 

appareil doivent être utilisées.

WARNING: DO NOT abuse glass door by 

striking or slamming shut.

       WARNING 

 

Do not attempt to substitute 

the materials used on this 

door, or replace cracked or 

broken glass. 

• Handle this glass with 

extreme care! Glass is 

susceptible to damage – Do 

not scratch or handle roughly 

while reinstalling the glass 

door frame.

• The glass door of this 

appliance must only be 

replaced as a complete 

unit as provided by the 

manufacturer. Do not attempt 

to replace broken, cracked or 

chipped glass separately. 

 

Do not attempt to touch 

the front enclosure glass 

with your hands while the 

fireplace is in use.

       WARNING 

Do not operate appliance with 

the glass front removed, cracked 

or broken.

       AVERTISSEMENT 

Ne pas utiliser l'appareil si le 

panneau frontal en verre n'est 

pas en place, est craqué ou 

brisé. 

f i r e - p a r t s . c o m

Summary of Contents for SDV35-2

Page 1: ...xactly a fire or explosion may result causing property damage personal injury or death HOT GLASS WILL CAUSE BURNS DO NOT TOUCH GLASS UNTIL COOLED NEVER ALLOW CHILDREN TO TOUCH GLASS UNE SURFACE VITR E...

Page 2: ...paring Appliance Vent Collar 13 Step 4 Installing Vent System 13 Vertical Termination Systems 14 Vent Section Length Chart 14 Vertical Vent Tables and Figures 17 Horizontal Termination System 19 Horiz...

Page 3: ...sed in the installation of this appliance Seules les trousses de garniture fournies par le fabricant doivent tre utilis es pour l installation de cet appareil This appliance complies with National Saf...

Page 4: ...OVINCIAL OR TERRITORIAL AUTHORITIES HAVING JURISDICTION AND IN ACCORDANCE WITH THE REQUIREMENTS OF THE CAN CGA B149 1 OR CAN CGA B149 2 INSTALLATION CODES REQUIREMENTS FOR THE COMMONWEALTHOFMASSACHUSE...

Page 5: ...om It is especially important to insulate outside chase cavity between studs and under floor on which appliance rests if floor is above ground level Gas line holes and other openings should be caulked...

Page 6: ...ion Storm Collar Concentric Vent Pipe Flashing 1 inch 25 4 mm Minimum Clearance to Combustibles Figure 4 Termination Heights for Vents Above Flat or Sloped Roofs Vertical Vent Termination Clearances T...

Page 7: ...c e m n o n o t e c n a r a e l C J e c n a i l p p a r e h t o y n a o t t e l n i r i a n o i t s u b m o c e h t s e c n a i l p p a r o f m c 5 1 s e h c n i 6 m c 0 3 s e h c n i 2 1 W k 3 h u t...

Page 8: ...minimize obstructions to the space above the appliance Do not insulate the space between the appliance and the area above it see Figure 7 The minimum height from the base of the appliance to the unde...

Page 9: ...materials must not be allowed to encroach the area defined by the appliance front face black sheet metal Never allow combustible materials to be positioned in front of or overlapping the appliance fa...

Page 10: ...EMPT from the 1 2 in clearance to combustible requirements for the firebox outer wrapper Combustible framing may be in direct contact with the nailing flanges and may be located closer than 1 2 in fro...

Page 11: ...51 Right Side View 14 43 1092 12 7 16 9 16 316 Inches Millimeters 5 29 1 2 749 19 406 35 1 8 892 37 5 32 944 Overall unit height Note J box can be relocated in either the right front or left front cor...

Page 12: ...ition Canada Step 2 ROUTING GAS LINE Route a 1 2 in 13 mm gas line to the left side of the appliance as shown in Figure 14 Gas lines must be routed constructed and made of materials that are in strict...

Page 13: ...USA or the current standards of CAN CGA B149 1 in Canada Ensure clearances are in accordance with local installation codes and the requirements of the gas supplier D gagement conforme aux codes d inst...

Page 14: ...1 0 1 0 5 0 6 6 8 1 5 5 1 0 0 0 0 4 4 5 0 9 1 5 7 8 5 1 1 0 0 0 4 5 5 6 9 1 5 7 3 6 1 0 1 0 0 4 5 5 5 0 2 5 2 1 7 1 0 1 1 5 0 7 7 0 2 5 2 7 1 0 0 0 6 0 6 5 1 1 2 5 2 6 7 1 1 0 0 6 0 7 5 7 1 2 5 2 1 8...

Page 15: ...h 3 pilot holes Slip the plain end over the locking channel end of a standard SV4 5 vent component the required distance and secure with three screws Maintain a minimum 1 in 25 mm clearance to combust...

Page 16: ...he required clearances to combustibles 1 in 25 mm at all sides for all vertical runs and 3 in 76 mm at the top 1 in 25 mm at sides and 1 in 25 mm at the bottom for all horizontal inclined runs H Frame...

Page 17: ...Spacer SF4 5VF Ceiling Firestop Spacer SV4 5VF Figure 30 Rear Vent ONE 90 DEGREE ELBOW This table shows a 1 V to 2 H ratio For every 1 foot of V vertical you are allowed 2 feet of H horizontal run up...

Page 18: ...feet 6 096 m Max V V1 H H1 40 ft 12 192 m Max meters meters Example If 20 feet of H horizontal vent run is needed then 4 feet minimum of V vertical vent will be required This table shows a 1 V to 5 H...

Page 19: ...outer pipe elements with the same procedure Sealant and securing screws are not required Note An elbow may also be attached to the appliance collar Attach in the same manner as you would a vent secti...

Page 20: ...ll or siding by more than the 1 1 4 in 32 mm as shown in Figure 36 SVHRK Snorkel Cap The snorkel cap is designed to be fitted into a basement window box The SVHRK cap is for use with flex vent The ver...

Page 21: ...ing SV4 5HT 2 termination kit HORIZONTAL VENT FIGURES TABLES Note Two 45 degree elbows may be used in place of one 90 degree elbow The same rise to run ratios as shown in the venting figures for 90 el...

Page 22: ...then 4 feet minimum of V vertical vent will be required This table shows a 1 V to 5 H ratio For every 1 foot of V vertical you are allowed 5 feet of H horizontal run up to a maximum horizontal run of...

Page 23: ...5 1 524 Elbow Only 5 1 524 1 0 305 10 3 048 2 0 610 15 4 572 3 0 914 20 6 096 4 1 219 meters TABLE L meters H Maximum 1 1 H H1 20 feet 6 096 m Max V V H H 40 ft 12 192 m Max Example If 20 feet of H h...

Page 24: ...inner adaptor collar approximately 1 2 inch from the end 3 Pull and extend the inner flexible vent pipe 4 Slide the inner flex pipe over the adaptor collar Ensure the flexible vent pipe completely eng...

Page 25: ...The gas valve is set in place and pre wired at the factory on both models Wiring see Figure 46 This unit is not provided with factory installed controls therefore one of the optional control switches...

Page 26: ...oor by sliding the hinge pin located at the door s left side to the right until it disengages from the left corner post hole Pull the door diagonally to the left away from the fireplace The control va...

Page 27: ...e pipes fittings can result in corrosion over time A Light the appliance refer to the lighting instructions label in the control compartment or in the Care and Operation Instructions manual B Brush al...

Page 28: ...e logs until the appliance installa tion has been completed the gas lineconnectedandtestedforleaks and the initial burner operation has been checked out Thesizeandpositionofthelogset was engineered to...

Page 29: ...wn Position the rear log on the brackets at the rear of the firebox with the log s notches directly over the brackets Position the right log log no 3 by inserting the pin from the rear log into the ho...

Page 30: ...is provided to aid you in achieving the correct air shutter adjustment for your installation Figure 54 Door Removal Removing the Glass Enclosure Panel see Figure 54 Remove the top radiant panel To acc...

Page 31: ...gures 65 and 66 All models must have hoods installed prior to operating Slide the hood into the slots on the lower edge of the radiant panel Figure 57 FINISHING REQUIREMENTS Wall Details Complete fini...

Page 32: ...raisse ou d huile Collez l tiquette sur la surface de la plaque de l interrupteur mural qui contr le le foyer Figure A ou du thermostat mural Figure B Choisissez la langue qui est principalement parl...

Page 33: ...246 SV4 5HF 10 Firestop Spacer Hori zontal rigid 3 1 1 spac ing 10 Pack H2247 SV4 5VF 10 Firestop Spacer Verti cal rigid 1 1 1 spac ing 10 Pack 96K92 SV4 5SP Support Plate INSTALLATION ACCESSORIES Lis...

Page 34: ...Small Square Termination for flex without flex vent Ref Instr 750204M INSTALLATION ACCESSORIES CONTINUED All compressed flex vents can be expanded up to two times Listed Secure Flex Components Cat Mod...

Page 35: ...the appliance see Page 30 WARNING This conversion kit shall be installed by a qualified service agency in accordance with the manufacturer s instructions and all applicable codes andrequirementsofthea...

Page 36: ...crews as shown in Figure 59 Tighten the screws to 25 in lb Step 8 Install the enclosed identification label to the valve body where it can be easily seen Step 9 Refer to Figure 60 and replace the pilo...

Reviews: