Superior SDV35-2 Installation Instructions Manual Download Page 36

SUPERIOR

®

  •  DIRECT VENT GAS FIREPLACES (SDV35-N-2)  •  INSTALLATION INSTRUCTIONS

A.

 Remove the orifice from the manifold and 

replace it with the one provided in the kit. See 

the following table for orifice sizes for natural 

and propane models. 

Figure 60

 illustrates 

the orifice. 

Use pipe joint compound or Teflon tape on 

all pipe fittings before installing (ensure 

propane resistant compounds are used in 

propane applications, do not use pipe joint 

compounds on flare fittings).

B.

 Retrieve the burner and hold the venturi 

tube above the orifice. Place the shutter 

adjusting rod in the propane slot of the 

shutter arm (see 

Figure 56

 on 

Page 31

). 

Set the burner assem bly into its position 

and secure the trapezoidal plate with the two 

screws previously removed. 

C.

 Reinstall the baffle with the two baffle 

securing screws.

Step 11.

 Reassemble the remaining 

components by reversing the procedures 

outlined in the 

Steps 1–7

.

Step 12

. Attach the conversion label provided 

in the conversion kit next to the rating plate 

on the appliance.

Step 13

. Turn on gas supply and test for gas 

leaks (refer to 

Page 27

).

Step 4.

 Carefully remove the logs. 

Exercise 

care so as not to break the logs

.

Step 5.

 Remove the burner.

A.

 Remove the sub floor.

B.

 Remove the two (2) screws securing the 

burner assembly.

C.

 Remove the burner assembly with 

attached venturi tube.

Ignition System

Step 6.

 

SIT Systems

—Refer to Figure 59 

and the instructions provided with the SIT 

Regulator Conversion Kit. Using a Torx T20 

driver (with 1/4 in. shank and center hole) 

or slotted screwdriver, remove and discard 

the three (3) pressure regulator mounting 

screws, pressure regulator tower, the 

diaphragm assembly (if applicable) and the 

spring. Discard all removed components.

Step 7.

 Install the new pressure regulator 

assembly using the supplied screws as 

shown in Figure 59. Tighten the screws to 

25 in-lb..

Step 8.

 Install the enclosed identification 

label to the valve body where it can be easily 

seen.

Step 9.

 Refer to 

Figure 60

 and replace the 

pilot orifice. 

Remove the pilot hood assembly to access 

the hexed pilot orifice. Remove and replace 

the orifice with the one provided with the kit. 

Exercise extreme care to prevent damage to 

or breakage of the igniter assembly.

Step 10.

 

Refer to 

Figure 60

 and replace the burner 

orifice. 

Step 14

. Relight the main burner. The lighting 

instructions can be found on the lighting 

label in the control compartment or in the 

Care and Operation Manual provided with 

the appliance. Verify proper burner ignition 

and operation. See Burner Adjustments and 

Burner Flame Appearance on 

Page 31

.

Inspect the pilot system for proper flame. The 

pilot flame should engulf the flame sensor as 

shown in 

Figure 50

 on 

Page 27

.

Step 15

. Using a manometer, test the inlet 

and manifold gas pressures. See 

Table 3

 on 

Page 4

.

ALWAYS TEST PRESSURES WITH THE 
VALVE REGULATOR CONTROL AT THE 
HIGHEST SETTING.

Figure 59: 

Orifice

Figure 58: Millivolt Valve

Pressure

Regulator

Remove

These

Components

Model

Series

Nat.Gas

drill size (inches)

Propane

drill size (inches)

SDV35-2

#44 (0.086 in.)*

60J80•

#55 (0.052 in.)*

19L52•

Table 13: Burner Orifice Sizes 

Elevation 0–4500 ft ( 0–1372 m)

* Standard size installed at factory

• Part /Cat. Number

Lennox Hearth Products

1508 Elm Hill Pike, Suite 108 • Nashville, TN  37210

Lennox Hearth Products reserves the right to make changes at any time, without notice, in design, 

materials, specifications, prices and also to discontinue colors, styles and products. 

Consult your local distributor for fireplace code information.

LENNOX

®

, the LENNOX design, DAVE LENNOX, the image of DAVE LENNOX and other related

LENNOX marks are registered or common law trademarks of Lennox Industries Inc. and are used

with permission.

Printed in U.S.A. © 2012 Lennox Hearth Products LLC

P/N  506009-03   Rev. NC   06/2012 

f i r e - p a r t s . c o m

Summary of Contents for SDV35-2

Page 1: ...xactly a fire or explosion may result causing property damage personal injury or death HOT GLASS WILL CAUSE BURNS DO NOT TOUCH GLASS UNTIL COOLED NEVER ALLOW CHILDREN TO TOUCH GLASS UNE SURFACE VITR E...

Page 2: ...paring Appliance Vent Collar 13 Step 4 Installing Vent System 13 Vertical Termination Systems 14 Vent Section Length Chart 14 Vertical Vent Tables and Figures 17 Horizontal Termination System 19 Horiz...

Page 3: ...sed in the installation of this appliance Seules les trousses de garniture fournies par le fabricant doivent tre utilis es pour l installation de cet appareil This appliance complies with National Saf...

Page 4: ...OVINCIAL OR TERRITORIAL AUTHORITIES HAVING JURISDICTION AND IN ACCORDANCE WITH THE REQUIREMENTS OF THE CAN CGA B149 1 OR CAN CGA B149 2 INSTALLATION CODES REQUIREMENTS FOR THE COMMONWEALTHOFMASSACHUSE...

Page 5: ...om It is especially important to insulate outside chase cavity between studs and under floor on which appliance rests if floor is above ground level Gas line holes and other openings should be caulked...

Page 6: ...ion Storm Collar Concentric Vent Pipe Flashing 1 inch 25 4 mm Minimum Clearance to Combustibles Figure 4 Termination Heights for Vents Above Flat or Sloped Roofs Vertical Vent Termination Clearances T...

Page 7: ...c e m n o n o t e c n a r a e l C J e c n a i l p p a r e h t o y n a o t t e l n i r i a n o i t s u b m o c e h t s e c n a i l p p a r o f m c 5 1 s e h c n i 6 m c 0 3 s e h c n i 2 1 W k 3 h u t...

Page 8: ...minimize obstructions to the space above the appliance Do not insulate the space between the appliance and the area above it see Figure 7 The minimum height from the base of the appliance to the unde...

Page 9: ...materials must not be allowed to encroach the area defined by the appliance front face black sheet metal Never allow combustible materials to be positioned in front of or overlapping the appliance fa...

Page 10: ...EMPT from the 1 2 in clearance to combustible requirements for the firebox outer wrapper Combustible framing may be in direct contact with the nailing flanges and may be located closer than 1 2 in fro...

Page 11: ...51 Right Side View 14 43 1092 12 7 16 9 16 316 Inches Millimeters 5 29 1 2 749 19 406 35 1 8 892 37 5 32 944 Overall unit height Note J box can be relocated in either the right front or left front cor...

Page 12: ...ition Canada Step 2 ROUTING GAS LINE Route a 1 2 in 13 mm gas line to the left side of the appliance as shown in Figure 14 Gas lines must be routed constructed and made of materials that are in strict...

Page 13: ...USA or the current standards of CAN CGA B149 1 in Canada Ensure clearances are in accordance with local installation codes and the requirements of the gas supplier D gagement conforme aux codes d inst...

Page 14: ...1 0 1 0 5 0 6 6 8 1 5 5 1 0 0 0 0 4 4 5 0 9 1 5 7 8 5 1 1 0 0 0 4 5 5 6 9 1 5 7 3 6 1 0 1 0 0 4 5 5 5 0 2 5 2 1 7 1 0 1 1 5 0 7 7 0 2 5 2 7 1 0 0 0 6 0 6 5 1 1 2 5 2 6 7 1 1 0 0 6 0 7 5 7 1 2 5 2 1 8...

Page 15: ...h 3 pilot holes Slip the plain end over the locking channel end of a standard SV4 5 vent component the required distance and secure with three screws Maintain a minimum 1 in 25 mm clearance to combust...

Page 16: ...he required clearances to combustibles 1 in 25 mm at all sides for all vertical runs and 3 in 76 mm at the top 1 in 25 mm at sides and 1 in 25 mm at the bottom for all horizontal inclined runs H Frame...

Page 17: ...Spacer SF4 5VF Ceiling Firestop Spacer SV4 5VF Figure 30 Rear Vent ONE 90 DEGREE ELBOW This table shows a 1 V to 2 H ratio For every 1 foot of V vertical you are allowed 2 feet of H horizontal run up...

Page 18: ...feet 6 096 m Max V V1 H H1 40 ft 12 192 m Max meters meters Example If 20 feet of H horizontal vent run is needed then 4 feet minimum of V vertical vent will be required This table shows a 1 V to 5 H...

Page 19: ...outer pipe elements with the same procedure Sealant and securing screws are not required Note An elbow may also be attached to the appliance collar Attach in the same manner as you would a vent secti...

Page 20: ...ll or siding by more than the 1 1 4 in 32 mm as shown in Figure 36 SVHRK Snorkel Cap The snorkel cap is designed to be fitted into a basement window box The SVHRK cap is for use with flex vent The ver...

Page 21: ...ing SV4 5HT 2 termination kit HORIZONTAL VENT FIGURES TABLES Note Two 45 degree elbows may be used in place of one 90 degree elbow The same rise to run ratios as shown in the venting figures for 90 el...

Page 22: ...then 4 feet minimum of V vertical vent will be required This table shows a 1 V to 5 H ratio For every 1 foot of V vertical you are allowed 5 feet of H horizontal run up to a maximum horizontal run of...

Page 23: ...5 1 524 Elbow Only 5 1 524 1 0 305 10 3 048 2 0 610 15 4 572 3 0 914 20 6 096 4 1 219 meters TABLE L meters H Maximum 1 1 H H1 20 feet 6 096 m Max V V H H 40 ft 12 192 m Max Example If 20 feet of H h...

Page 24: ...inner adaptor collar approximately 1 2 inch from the end 3 Pull and extend the inner flexible vent pipe 4 Slide the inner flex pipe over the adaptor collar Ensure the flexible vent pipe completely eng...

Page 25: ...The gas valve is set in place and pre wired at the factory on both models Wiring see Figure 46 This unit is not provided with factory installed controls therefore one of the optional control switches...

Page 26: ...oor by sliding the hinge pin located at the door s left side to the right until it disengages from the left corner post hole Pull the door diagonally to the left away from the fireplace The control va...

Page 27: ...e pipes fittings can result in corrosion over time A Light the appliance refer to the lighting instructions label in the control compartment or in the Care and Operation Instructions manual B Brush al...

Page 28: ...e logs until the appliance installa tion has been completed the gas lineconnectedandtestedforleaks and the initial burner operation has been checked out Thesizeandpositionofthelogset was engineered to...

Page 29: ...wn Position the rear log on the brackets at the rear of the firebox with the log s notches directly over the brackets Position the right log log no 3 by inserting the pin from the rear log into the ho...

Page 30: ...is provided to aid you in achieving the correct air shutter adjustment for your installation Figure 54 Door Removal Removing the Glass Enclosure Panel see Figure 54 Remove the top radiant panel To acc...

Page 31: ...gures 65 and 66 All models must have hoods installed prior to operating Slide the hood into the slots on the lower edge of the radiant panel Figure 57 FINISHING REQUIREMENTS Wall Details Complete fini...

Page 32: ...raisse ou d huile Collez l tiquette sur la surface de la plaque de l interrupteur mural qui contr le le foyer Figure A ou du thermostat mural Figure B Choisissez la langue qui est principalement parl...

Page 33: ...246 SV4 5HF 10 Firestop Spacer Hori zontal rigid 3 1 1 spac ing 10 Pack H2247 SV4 5VF 10 Firestop Spacer Verti cal rigid 1 1 1 spac ing 10 Pack 96K92 SV4 5SP Support Plate INSTALLATION ACCESSORIES Lis...

Page 34: ...Small Square Termination for flex without flex vent Ref Instr 750204M INSTALLATION ACCESSORIES CONTINUED All compressed flex vents can be expanded up to two times Listed Secure Flex Components Cat Mod...

Page 35: ...the appliance see Page 30 WARNING This conversion kit shall be installed by a qualified service agency in accordance with the manufacturer s instructions and all applicable codes andrequirementsofthea...

Page 36: ...crews as shown in Figure 59 Tighten the screws to 25 in lb Step 8 Install the enclosed identification label to the valve body where it can be easily seen Step 9 Refer to Figure 60 and replace the pilo...

Reviews: