Superior SDV35-2 Installation Instructions Manual Download Page 12

12

NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.

SUPERIOR

®

  •  DIRECT-VENT GAS FIREPLACES (SDV35-N-2)  •  INSTALLATION INSTRUCTIONS

FIREPLACE FRAMING SPECIFICATIONS

Schedule 40 Pipe

Length (feet)

Natural

Gas

Propane

Gas

0–10

1/2 in.

3/8 in.

10–40

1/2 in.

1/2 in.

40–100

1/2 in.

1/2 in.

100–150

3/4 in.

1/2 in.

150–200

3/4 in.

1/2 in.

Table 6: Schedule 40 Black Iron Pipe—

Inside Diameter

•  See 

Massachusetts Requirements

 on 

Page 4

 for additional requirements for 

installations in the state of Massachusetts 

in the USA.

•  The gas supply line should Not be 

connected to the appliance until 

Step 6

 

(

Page 26

).

•  A pipe joint compound rated for gas 

should be used on the threaded joints. 

Ensure propane resistant compounds are 

used in propane applications

. Be very 

careful that the pipe compound does not 

get inside the pipe.

•  It is recommended to install a sediment 

trap in the supply line as close as possible 

to the appliance.

•  Check with local building official for local 

code requirements.

IMPORTANT: If propane is used, be aware 

that if tank size is too small (i.e. under 

100 lbs, if this is the only gas appliance 

in the dwelling. Ref. NPFA 58), there 

may be loss of pressure, resulting in 

insufficient fuel delivery (which can result 

in sooting, severe delayed ignition or other 

malfunctions). Any damage resulting from 

an improper installation, such as this, is 

not covered under the limited warranty.

Proper Sizing of Gas Line

Properly size and route the gas supply 

line from the supply regulator to the area 

where the appliance is to be installed per 

requirements outlined in the National Fuel 

Gas Code, NFPA 54—latest edition (USA) or 

CAN/CGA-B149.1—latest edition (Canada).

Step 2. ROUTING GAS LINE 

Route a 1/2 in. (13 mm) gas line to the 

left side of the appliance as shown in

 

Figure 14

. Gas lines must be routed, 

constructed and made of materials that 

are in strict accordance with local codes 

and regulations. All appliances are factory-

equipped with a flexible gas line connector 

and 1/2 in. shutoff valve. 

(See 

Step 7 

on 

Page 26

).

Never use galvanized or plastic pipe. Refer to 

Table 6

 for proper sizing of the gas supply 

line, if black iron pipe is being used. Gas lines 

must be routed, constructed and made of 

materials that are in strict accordance with 

local codes and regulations. We recommend 

that a qualified individual such as a plumber 

or gas fitter be hired to correctly size and 

route the gas supply line to the appliance. 

Installing a gas supply line from the fuel 

supply to the appliance involves numerous 

considerations of materials, protection, 

sizing, locations, controls, pressure, 

sediment, and more. Certainly no one 

unfamiliar and unqualified should attempt 

sizing or installing gas piping.

Figure 13: Corner Framing with Horizontal Termination

Also see 

Figure 12.

Figure 14: Route Gas Line

3 in.

(76 mm)

Left Side Front

Corner of Fireplace

Framing

6-1/2 in.

(152 mm)

Pipe Coupling

(Recommended)

Note:

• Rear Vent Applications in Corner Installations: 

The horizontal vent length 

(from 

a

 to 

b

) must not exceed 28 inches (711 mm).

•  Dimensions

 D through F

 occur when one 45-degree elbow is connected 

directly to the appliance collar. 

Notes:

•  All appliances are factory-equipped with 

a flexible gas line connector and 1/2 inch 

shutoff valve (see 

Figure 48

 on 

Page 27

).

Model 

A

B

C

D

E

F

SDV35-N-2

in. 

42 1/4

57 1/2

40 5/8

19 3/16

28 3/4

6 1/8

mm

1073

1461

1032

487

730

156

C

Back wall of chase/enclosure (including any finishing materials)

 7 in.

(178 mm)

Rear Vent

D

E

F

A

B

Top Vent

b

a

f i r e - p a r t s . c o m

Summary of Contents for SDV35-2

Page 1: ...xactly a fire or explosion may result causing property damage personal injury or death HOT GLASS WILL CAUSE BURNS DO NOT TOUCH GLASS UNTIL COOLED NEVER ALLOW CHILDREN TO TOUCH GLASS UNE SURFACE VITR E...

Page 2: ...paring Appliance Vent Collar 13 Step 4 Installing Vent System 13 Vertical Termination Systems 14 Vent Section Length Chart 14 Vertical Vent Tables and Figures 17 Horizontal Termination System 19 Horiz...

Page 3: ...sed in the installation of this appliance Seules les trousses de garniture fournies par le fabricant doivent tre utilis es pour l installation de cet appareil This appliance complies with National Saf...

Page 4: ...OVINCIAL OR TERRITORIAL AUTHORITIES HAVING JURISDICTION AND IN ACCORDANCE WITH THE REQUIREMENTS OF THE CAN CGA B149 1 OR CAN CGA B149 2 INSTALLATION CODES REQUIREMENTS FOR THE COMMONWEALTHOFMASSACHUSE...

Page 5: ...om It is especially important to insulate outside chase cavity between studs and under floor on which appliance rests if floor is above ground level Gas line holes and other openings should be caulked...

Page 6: ...ion Storm Collar Concentric Vent Pipe Flashing 1 inch 25 4 mm Minimum Clearance to Combustibles Figure 4 Termination Heights for Vents Above Flat or Sloped Roofs Vertical Vent Termination Clearances T...

Page 7: ...c e m n o n o t e c n a r a e l C J e c n a i l p p a r e h t o y n a o t t e l n i r i a n o i t s u b m o c e h t s e c n a i l p p a r o f m c 5 1 s e h c n i 6 m c 0 3 s e h c n i 2 1 W k 3 h u t...

Page 8: ...minimize obstructions to the space above the appliance Do not insulate the space between the appliance and the area above it see Figure 7 The minimum height from the base of the appliance to the unde...

Page 9: ...materials must not be allowed to encroach the area defined by the appliance front face black sheet metal Never allow combustible materials to be positioned in front of or overlapping the appliance fa...

Page 10: ...EMPT from the 1 2 in clearance to combustible requirements for the firebox outer wrapper Combustible framing may be in direct contact with the nailing flanges and may be located closer than 1 2 in fro...

Page 11: ...51 Right Side View 14 43 1092 12 7 16 9 16 316 Inches Millimeters 5 29 1 2 749 19 406 35 1 8 892 37 5 32 944 Overall unit height Note J box can be relocated in either the right front or left front cor...

Page 12: ...ition Canada Step 2 ROUTING GAS LINE Route a 1 2 in 13 mm gas line to the left side of the appliance as shown in Figure 14 Gas lines must be routed constructed and made of materials that are in strict...

Page 13: ...USA or the current standards of CAN CGA B149 1 in Canada Ensure clearances are in accordance with local installation codes and the requirements of the gas supplier D gagement conforme aux codes d inst...

Page 14: ...1 0 1 0 5 0 6 6 8 1 5 5 1 0 0 0 0 4 4 5 0 9 1 5 7 8 5 1 1 0 0 0 4 5 5 6 9 1 5 7 3 6 1 0 1 0 0 4 5 5 5 0 2 5 2 1 7 1 0 1 1 5 0 7 7 0 2 5 2 7 1 0 0 0 6 0 6 5 1 1 2 5 2 6 7 1 1 0 0 6 0 7 5 7 1 2 5 2 1 8...

Page 15: ...h 3 pilot holes Slip the plain end over the locking channel end of a standard SV4 5 vent component the required distance and secure with three screws Maintain a minimum 1 in 25 mm clearance to combust...

Page 16: ...he required clearances to combustibles 1 in 25 mm at all sides for all vertical runs and 3 in 76 mm at the top 1 in 25 mm at sides and 1 in 25 mm at the bottom for all horizontal inclined runs H Frame...

Page 17: ...Spacer SF4 5VF Ceiling Firestop Spacer SV4 5VF Figure 30 Rear Vent ONE 90 DEGREE ELBOW This table shows a 1 V to 2 H ratio For every 1 foot of V vertical you are allowed 2 feet of H horizontal run up...

Page 18: ...feet 6 096 m Max V V1 H H1 40 ft 12 192 m Max meters meters Example If 20 feet of H horizontal vent run is needed then 4 feet minimum of V vertical vent will be required This table shows a 1 V to 5 H...

Page 19: ...outer pipe elements with the same procedure Sealant and securing screws are not required Note An elbow may also be attached to the appliance collar Attach in the same manner as you would a vent secti...

Page 20: ...ll or siding by more than the 1 1 4 in 32 mm as shown in Figure 36 SVHRK Snorkel Cap The snorkel cap is designed to be fitted into a basement window box The SVHRK cap is for use with flex vent The ver...

Page 21: ...ing SV4 5HT 2 termination kit HORIZONTAL VENT FIGURES TABLES Note Two 45 degree elbows may be used in place of one 90 degree elbow The same rise to run ratios as shown in the venting figures for 90 el...

Page 22: ...then 4 feet minimum of V vertical vent will be required This table shows a 1 V to 5 H ratio For every 1 foot of V vertical you are allowed 5 feet of H horizontal run up to a maximum horizontal run of...

Page 23: ...5 1 524 Elbow Only 5 1 524 1 0 305 10 3 048 2 0 610 15 4 572 3 0 914 20 6 096 4 1 219 meters TABLE L meters H Maximum 1 1 H H1 20 feet 6 096 m Max V V H H 40 ft 12 192 m Max Example If 20 feet of H h...

Page 24: ...inner adaptor collar approximately 1 2 inch from the end 3 Pull and extend the inner flexible vent pipe 4 Slide the inner flex pipe over the adaptor collar Ensure the flexible vent pipe completely eng...

Page 25: ...The gas valve is set in place and pre wired at the factory on both models Wiring see Figure 46 This unit is not provided with factory installed controls therefore one of the optional control switches...

Page 26: ...oor by sliding the hinge pin located at the door s left side to the right until it disengages from the left corner post hole Pull the door diagonally to the left away from the fireplace The control va...

Page 27: ...e pipes fittings can result in corrosion over time A Light the appliance refer to the lighting instructions label in the control compartment or in the Care and Operation Instructions manual B Brush al...

Page 28: ...e logs until the appliance installa tion has been completed the gas lineconnectedandtestedforleaks and the initial burner operation has been checked out Thesizeandpositionofthelogset was engineered to...

Page 29: ...wn Position the rear log on the brackets at the rear of the firebox with the log s notches directly over the brackets Position the right log log no 3 by inserting the pin from the rear log into the ho...

Page 30: ...is provided to aid you in achieving the correct air shutter adjustment for your installation Figure 54 Door Removal Removing the Glass Enclosure Panel see Figure 54 Remove the top radiant panel To acc...

Page 31: ...gures 65 and 66 All models must have hoods installed prior to operating Slide the hood into the slots on the lower edge of the radiant panel Figure 57 FINISHING REQUIREMENTS Wall Details Complete fini...

Page 32: ...raisse ou d huile Collez l tiquette sur la surface de la plaque de l interrupteur mural qui contr le le foyer Figure A ou du thermostat mural Figure B Choisissez la langue qui est principalement parl...

Page 33: ...246 SV4 5HF 10 Firestop Spacer Hori zontal rigid 3 1 1 spac ing 10 Pack H2247 SV4 5VF 10 Firestop Spacer Verti cal rigid 1 1 1 spac ing 10 Pack 96K92 SV4 5SP Support Plate INSTALLATION ACCESSORIES Lis...

Page 34: ...Small Square Termination for flex without flex vent Ref Instr 750204M INSTALLATION ACCESSORIES CONTINUED All compressed flex vents can be expanded up to two times Listed Secure Flex Components Cat Mod...

Page 35: ...the appliance see Page 30 WARNING This conversion kit shall be installed by a qualified service agency in accordance with the manufacturer s instructions and all applicable codes andrequirementsofthea...

Page 36: ...crews as shown in Figure 59 Tighten the screws to 25 in lb Step 8 Install the enclosed identification label to the valve body where it can be easily seen Step 9 Refer to Figure 60 and replace the pilo...

Reviews: