Some common questions when paralleling inverters:
What is the sequence to install/connect/commission?
First of all, leave the main supplies off. Next, connect all communication cables, set up all LCDs and then,
finally, turn-on the main supplies.
What are the indications that the communication and the system are ok or not?
Parallel errors will be shown as fault F46 on the display.
What are the consequences of not setting one inverter in a parallel mode?
It can damage the inverter.
What are the consequences of having more than one master, or none set to master for that
matter?
It can damage the inverter. There are cases in which it is possible to have more than one master. For
example, as aforementioned, six inverters paralleled in a three phase utility grid (three masters)..
What are the consequences of setting A, B, or C phase wrong on the LCD?
It can damage the inverter. Recommend checking the phase rotation with a meter before switching on.
What are the consequences of factory resetting, power cycling, or firmware updating one inverter
in a parallel system?
There is no consequence, but the master inverter will keep controlling the slaves.
What consequences for changing ALL/ANY settings while operating in parallel mode?
It can damage the inverter and fault F46 will be indicated on the display.