17
Hybrid Parity (Super) Inverter 3.6kW/5.5kW/8.8kW Plus Parallel Version
www.sunsynk.com
``
IMPORTANT !!!
If the CT coil is fitted in the wrong
way then this variable will have
negative instead of positive
values when the power is flowing
into the house/inverter. Also, the
inverter export limiting function
will not work properly.
IMPORTANT !!!
See below for information to determine if the CT coil is connected the correct way around:
1.
First of all, ensure that the CT is measuring some power flowing into the house/inverter by switching
off the "Time Of Use" setting and disconnecting the PV panels.
2.
Next, click on the "Battery Gauge", (5) to show the "System Status" screen below.
3.
Ensure that the "CT" or "HM" power value is positive and in black color. If it shows a negative value
then either turn the CT coil 180° or swap the CT coil wires around where they connect to the
inverter.