Hybrid Parity (Super) Inverter 3.6kW/5.5kW/8.8kW Plus Parallel Version
www.sunsynk.com
``
4.4. Status Page
To access the Status page, click on the “Battery” or “AC Load” dial on the Home page.
What this page displays:
Total solar power produced
MPPT 1 power/voltage/current
MPPT 2 power/voltage/current
Grid power
Grid frequency
Grid voltage
Grid current
Inverter power
Inverter frequency
Inverter voltage
Inverter current
Load power
Load voltage
Battery power charge/discharge
Battery SOC
Battery voltage
Battery current
Battery temperature
Solar Column:
Shows total PV p
ower at the top and then details of each of the two MPPT’s below L1 &
L2 voltage.
Grid Column:
Shows grid total power, frequency, voltage, and current. When selling to grid the power is
negative. When receiving from the grid the power is positive. If the sign of the grid and HM powers are
not the same when the PV is disconnected and the inverter is only taking energy from the grid and using
the HM CT connected to Limit-2 then please reverse the polarity of the HM current sensor.
Important
:
See section on CT coil.
Inverter Column:
Showing inverter total power, frequency, L1, L2, voltage, current, and power.
Load Column:
Showing total load power, load voltage, and power on L1 and L2.
Battery Column:
Showing total power from the battery, battery SOC, battery voltage, battery current
(negative means charge, positive means discharge) battery temperature (shows zero if the battery
temperature sensor is not connected). DC transformer temperature and AC heatsink temperature (When
the temperature reaches 90°C it will show in red and start deteriorating when it reaches 110°C. Next, the
inverter will shut down to allow it to cool and reduce its temperature.