4.16. Advanced Settings for Paralleling Inverters
To configure multi-
inverter settings click on the “Advance” icon.
Set the Modbus SN for paralleling
The Sunsynk parity inverter can be wired standalone or where more power is required it can be connected
in parallel either single or 3 phase configuration. The maximum number of 8.8kW inverters that can be
paralleled in a single phase utility grid is three (26.4kW) and the maximum number that can be paralleled
in a three phase utility grid is nine (79.2kW).
To parallel six inverters in a three phase utility grid is necessary to set three inverters as master and three
as slaves:
Phase A: Master A and Slave A
Phase B: Master B and Slave B
Phase C: Master C and Slave C
For stability, all the batteries need to be connected in parallel. It is recommended a minimum cable size
of 50mm diameter with fuse isolators to each inverter.
Each invert will require a fuse isolator with surge protection and each group circuit will require an RCD.
If the batteries as supplying power to the main load during the outage then a change over switch will also
be required or a split load can be used.