Electrical Specifications
Value
AC current, maximum for main cabinet (5300 W) 26.5A total
Power Cords
Description
Storage controller 0
2 power cords, rated at 10 A each, N+1 redundancy
Storage controller 1
2 power cords, rated at 10 A each, N+1 redundancy
Main cabinet
6 power cords, rated at 16 A each, divided into 2 separate circuits of 3 cords. Each
circuit provides N+1 redundancy
Caution
- The electrical power to the system must be controlled by external breaker switches.
Do not plug in any power cables. Only power on the system by following the instructions in the
Powering On and Configuration
section of the
Sun ZFS Storage 7x20 Installation Guide
available at
http://wikis.sun.com/display/fishworks. (
http://wikis.sun.com/display/
fishworks.
)
Two separate electrical sources are required for redundant operation of the storage system main
cabinet, as shown in the following figure.
Cabinet
Sun ZFS Storage 7x20 Appliance Installation Guide • November 2010