5-1
C H A P T E R
5
Replacing Chassis Components
This chapter provides instructions for replacing chassis components. Topics include:
■
Section 5.1, “Replacing the Air Filter” on page 5-1
■
Section 5.2, “Replacing a Power Supply” on page 5-3
■
Section 5.3, “Replacing the System Fan Assembly (FT0)” on page 5-6
■
Section 5.4, “Replacing the Hard Drive Fan Assembly (FT1)” on page 5-9
■
Section 5.5, “Replacing the FB-DIMM Fan Assembly (FT2)” on page 5-14
■
Section 5.6, “Replacing the Alarm Board” on page 5-15
■
Section 5.7, “Replacing the LED Board” on page 5-17
■
Section 5.8, “Replacing the Power Board” on page 5-22
5.1
Replacing the Air Filter
Server filter maintenance is dependent on the environmental air quality in which the
server is installed. The filter should be checked, at a minimum, annually and cleaned
or replaced if there is evidence of airflow blockage. In environments with high
particulate matter, the filter should be checked, cleaned or replaced more often.
Should the filter require cleaning, remove the filter from the server. See
Section 5.1.1,
“Removing the Air Filter” on page 5-1
. Take the filter to an open area and blow the
particles from the filter using a can of compressed air. Do not use a coarse brush or
anything abrasive since they may damage the filter.
5.1.1
Removing the Air Filter
1. Press the green tabs on both sides of the bezel and pull forward and down
(
FIGURE 5-1
).
Summary of Contents for Netra T5220
Page 1: ...Sun Netra T5220 Server Service Manual Part No E21359 02 January 2012...
Page 14: ...1 4 Sun Netra T5220 Server Service Manual January 2012 FIGURE 1 1 Diagnostic Flowchart...
Page 156: ...5 26 Sun Netra T5220 Server Service Manual January 2012...
Page 171: ...Appendix A Signal Pinouts A 7...
Page 172: ...A 8 Sun Netra T5220 Server Service Manual January 2012...