Section 6
SUPERVISOR II
30
S
Communications Baud Rate
--- This
should always be selected to 9600 baud
for all sequencing modes. It may be lower
for slave or monitoring modes.
BAUDRATE
9600
S
Sequence method
-- This parameter sets
the method used for sequencing. The
choices
are
DISABLED,
REMOTE,
SLAVE, HOURS, COM ID#. See the Se-
quencing
&
Protocol
Manual
(P/N
02250057--696) for details about these
modes.
SEQUENCE
HOURS
S
Drain interval
-- The time between actua-
tion of the drain valve.
DRN INTV
10 MIN
S
Drain time
-- The amount of time that the
drain valve is actuated.
DRN TIM
1 SEC
S
Last Communication Number
-- Used
only for sequencing, see Sequencing &
Protocol Manual for details.
LAST COM
3
S
Lowest Allowable Pressure
-- Used only
for sequencing, see Sequencing & Protocol
Manual for details.
LOWEST
90 PSI
S
Recovery Time
-- Used only for sequenc-
ing, see Sequencing & Protocol Manual for
details.
RECOVER
10 SEC
S
Rotate Time
-- Used only for sequencing,
see Sequencing & Protocol Manual for de-
tails.
ROTATE
50
S
Machine Capacity
-- Used only for se-
quencing, see Sequencing & Protocol
Manual for details.
CAPACITY
100
S
Sequence Hours
-- Used only for se-
quencing, see Sequencing & Protocol
Manual for details.
SEQ HRS
1000
6.6 OPERATING THE COMPRESSOR
Before operating the compressor the operating pa-
rameters must be setup. See the previous section
on operating parameter setup.
MANUAL OPERATION MODE
In this mode the compressor will run indefinitely, as
long as temperatures and pressure remain within
the valid operating ranges, and the motor overload
or emergency stop contacts are not tripped. Press-
ing the “
I
”will turn on the compressor and put it in
manual mode. If the compressor is already running,
but in automatic mode, pressing “
I
” will switch op-
eration to manual. Pressing “
I
” while already running
in manual mode will cause the Supervisor to turn off
the common fault relay, if engaged, and clear any
maintenance indicators.
To stop the compressor, press “
O
”. If the compres-
sor is already off when “
O
” is pressed, the common
fault relay will be turned off, if engaged, and it will try
to clear the alarm and maintenance indicators. Re-
gardless of what the compressor is doing, pressing
“
O
” puts the Supervisor in manual stop mode.
AUTOMATIC OPERATION MODE
In this mode the compressor will start if line pressure
(P2) is less than the
LOAD
parameter. It will stop if
the compressor runs unloaded for the number of
minutes indicated by the
UNLD TIM
parameter . To
put the compressor in automatic mode press “ ”. If
P2 is already less than
LOAD
the compressor will
start immediately, otherwise the system status will
indicate
STANDBY
and the LED marked
AUTO
will
flash.
If the compressor is already running, but in continu-
ous mode, pressing “ ” will switch operation to au-
tomatic. Pressing “ ” while already running in auto-
matic mode will cause the Supervisor to turn off the
common fault relay, if engaged, and clear any main-
tenance indicators.
In automatic mode the compressor can be stopped
manually by pressing
O
. Stopping the compressor
using
O
will put the Supervisor in manual stop mode.
Regardless of whether in “automatic” or “manual”
mode, control of the load solenoid will be based on
the parameters
UNLD
and
LOAD.
This operation is
as follows:
P2 > UNLD ----> load solenoid turned off
Summary of Contents for LS-20S
Page 6: ...NOTES...
Page 23: ...Section 3 SPECIFICATIONS 17 Figure 3 1A Identification Air cooled Model Prior to June 1 2000...
Page 24: ...Section 3 SPECIFICATIONS 18 Figure 3 1B Identification Air cooled Model After June 1 2000...
Page 25: ...Section 3 SPECIFICATIONS 19 Figure 3 1C Identification Water cooled Model...
Page 26: ...20 NOTES...
Page 31: ...25 NOTES...
Page 76: ...Section 8 PARTS LIST 70 8 16 ELECTRICAL BOX 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16...
Page 84: ...Section 8 PARTS LIST 78 8 20 DECAL GROUP 1 2 3 4 5 6 7 8 9 10 11 12 13 14...
Page 86: ...Section 8 PARTS LIST 80 8 20 DECAL GROUP 15 16 17 18 19 20 21 22 23 24...
Page 88: ...Section 8 PARTS LIST 82 8 20 DECAL GROUP 25 26 27 28 29...
Page 90: ...Section 8 PARTS LIST 84 8 20 DECAL GROUP 30 31 32...
Page 92: ...Section 8 PARTS LIST 86 8 21 DECAL LOCATIONS 1 2 3 4 5 6 7 8 9 10 12 11 15 16 17 18 12 13 14...
Page 94: ...Section 8 PARTS LIST 88 8 21 DECAL LOCATIONS 9 1 2 3 4 5 6 7 8 10 11 WATER COOLED MODEL 12 13...
Page 96: ...Section 8 PARTS LIST 90 8 21 DECAL LOCATIONS 1 2 3 5 6 7 4...
Page 98: ...Section 8 PARTS LIST 92 8 22 WIRING DIAGRAM STANDARD FULL VOLTAGE SUPERVISOR II DELUXE...
Page 99: ...Section 8 PARTS LIST 93 8 23 WIRING DIAGRAM STANDARD WYE DELTA SUPERVISOR II DELUXE...
Page 100: ...Section 8 PARTS LIST 94 8 24 WIRING DIAGRAM STANDARD WYE DELTA SUPERVISOR II DELUXE EUROPE...
Page 101: ...NOTES...