Section 6
SUPERVISOR II
29
presence of an alarm.
MOTOR
-- If flashing, indicates the motor overload
contact has opened.
INLET FILTER
-- If flashing, indicates that inlet filter
maintenance is needed.
OIL FILTER
-- If flashing, indicates that oil filter
maintenance is needed.
POWER ON
-- Lit if 120VAC power is applied to the
Supervisor II.
ON
-- If lit steady, the compressor is running. If flash-
ing, indicates that the compressor is armed but
stopped because of restart timer not expired, re-
mote stop or sequence stop. The compressor may
start at any time.
AUTO
-- If lit steady, the compressor is running and
in auto mode. If flashing, indicates that the compres-
sor is armed but stopped because of restart timer
not expired, remote stop or sequence stop. The
compressor may start at any time.
6.5 SUPERVISOR
II
OPERATING PARAMETERS--
SET UP
Pressing the program key enters parameter dis-
play and edit mode. To move to the next parameter
press the program key. To increment a parameter
press the up arrow key or logo key. The logo key
will increment by 10. To decrement the value press
the down arrow key.
The parameters are displayed in the following or-
der:
S
Unload pressure
--- The pressure where
the machine is unloaded. For example if
this parameter is set to 110 psi (7.6 bar) the
machine will unload when the line pressure
is above 110 psi (7.6 bar).
UNLOAD
100 PSI
S
Load differential
--- The pressure differ-
ential below the unload pressure where the
machine is loaded. For example if the un-
load pressure is set to 110 psi (7.6 bar) and
the load differential is set to 10 psid (0.7
bar), the machine will load when the line
pressure goes below 100 psi (6.9 bar).
LOAD
10 PSI
S
P1 Max
--- Maximum sump pressure. An
alarm and shut down will occur when the
sump pressure rises above this pressure.
P1 MAX
135 PSI
S
Wye to delta transition timer
--- For full
voltage starters this parameter is set to
zero.
WYE DELT
10 SEC
S
Restart time
--- Time to wait after powerup
before starting machine. This parameter is
used to keep several machines from start-
ing at the same time after power up, or to
delay start until other equipment is started.
If disabled the machine will not automati-
cally start after power up.
RST TIME
10 SEC
S
Unload Stop Timer
--- If the machine is
running in AUTO mode, this parameter
specifies the amount of time that the ma-
chine will run unloaded before shutting off.
If the time is set less than 15 minutes (five
minutes, for example), there may be times
when the machine will run unloaded for
more than five minutes. This is because
there is another timer that keeps the ma-
chine from being started more than four
times an hour.
UNLD TIM
15 MIN
S
Language select
--- English, German,
Spanish, Italian and French may be se-
lected for display language.
LANGUAGE
ENGLISH
S
Units
--- English or metric units may be se-
lected.
UNITS
ENGLISH
S
Communications ID #
--- This is the net-
work address of a machine. If there is more
than one machine connected to the net-
work, each machine must have a unique
number.
COM ID #
1
Summary of Contents for LS-20S
Page 6: ...NOTES...
Page 23: ...Section 3 SPECIFICATIONS 17 Figure 3 1A Identification Air cooled Model Prior to June 1 2000...
Page 24: ...Section 3 SPECIFICATIONS 18 Figure 3 1B Identification Air cooled Model After June 1 2000...
Page 25: ...Section 3 SPECIFICATIONS 19 Figure 3 1C Identification Water cooled Model...
Page 26: ...20 NOTES...
Page 31: ...25 NOTES...
Page 76: ...Section 8 PARTS LIST 70 8 16 ELECTRICAL BOX 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16...
Page 84: ...Section 8 PARTS LIST 78 8 20 DECAL GROUP 1 2 3 4 5 6 7 8 9 10 11 12 13 14...
Page 86: ...Section 8 PARTS LIST 80 8 20 DECAL GROUP 15 16 17 18 19 20 21 22 23 24...
Page 88: ...Section 8 PARTS LIST 82 8 20 DECAL GROUP 25 26 27 28 29...
Page 90: ...Section 8 PARTS LIST 84 8 20 DECAL GROUP 30 31 32...
Page 92: ...Section 8 PARTS LIST 86 8 21 DECAL LOCATIONS 1 2 3 4 5 6 7 8 9 10 12 11 15 16 17 18 12 13 14...
Page 94: ...Section 8 PARTS LIST 88 8 21 DECAL LOCATIONS 9 1 2 3 4 5 6 7 8 10 11 WATER COOLED MODEL 12 13...
Page 96: ...Section 8 PARTS LIST 90 8 21 DECAL LOCATIONS 1 2 3 5 6 7 4...
Page 98: ...Section 8 PARTS LIST 92 8 22 WIRING DIAGRAM STANDARD FULL VOLTAGE SUPERVISOR II DELUXE...
Page 99: ...Section 8 PARTS LIST 93 8 23 WIRING DIAGRAM STANDARD WYE DELTA SUPERVISOR II DELUXE...
Page 100: ...Section 8 PARTS LIST 94 8 24 WIRING DIAGRAM STANDARD WYE DELTA SUPERVISOR II DELUXE EUROPE...
Page 101: ...NOTES...