Connecting Dynaline
™
3 to a Standby Generator
A Dynaline
™
3 feature of particular importance to the nursing home/assisted
living industry is its low amp draw in the heating cycle, made possible by
its high efficiency gas heating. This creates an opportunity for the facility
to install a smaller, less costly standby emergency power generator, without
forfeiting zone temperature control on the heating cycle.
Dynaline 3 incorporates an A/C compressor lock-out capability.
This feature allows the compressor circuit to be locked out when facility
power is supplied by a standby emergency power generator. This is done
by routing 24-volt lead wires from a 208/230/24 V.A.C. transformer
(NOTE: Field supplied transformer to be powered by the standby generator.)
to the 1/4" spade terminals on the module board. (See
Figure 29
for
Ladder Diagram of typical standby generator electric service.)