Suburban Dynaline 3 A&E Manual 12/2016 Rev.1

32

Built-in Thermostat Control – Cooling Mode

1. Depress “System” key pad until cool lamp is illuminated. (See 

Figure 31

.)

2. Depress “Fan” key pad until desired speed lamp is illuminated. 

 (See 

Figure 31

.)

3. Set thermostat to desired setting by depressing temperature-indicating  

 

  arrows until desired temperature is displayed.
4. If the thermostat circuit is closed at the setting chosen in Step #3, the 

  cooling cycle begins.  

NOTE:

 On initial start-up, the compressor will not be energized for five (5) 

minutes even though the system functions have been properly selected. 

This is to protect the compressor. This feature can be overridden by pressing the 

“System” and “Cooler” pads at the same time.

NOTE:

 Whenever the outside temperature is below 65°F and the humidity 

is high, frost could form on the evaporator coil during extended cooling 

operation. To eliminate frost formation, a de-ice switch in the compressor 

circuit will sense a frost condition and open the compressor circuit. Upon 

temperature rise, the switch will close and the compressor will again come 

on provided that the thermostat is still calling for cooling.

NOTE:

 Dynaline

 3 has a built-in 5-minute delay between compressor cycles. 

Anytime the compressor cycle is interrupted either manually, through the 

thermostat, a power interruption, etc., the compressor will not restart for 

5 minutes. Also, the A/C compressor has a minimum one-minute run time.

Remote Thermostat Control – Heat Mode 

Initial Lighting Instructions

  

1. Set wall thermostat to “Heat Mode.”
2. Open the manual shut-off valve. The valve is fully open when the 

  handle is level or parallel to the gas line. Never attempt to operate    

unit with manual valve partially closed.
3. Set the wall thermostat at desired setting.
4. Select AUTO/FAN operation.
5. Using the “System” key pad, depress “Fan” key until desired speed lamp  

  is illuminated.

NOTE: 

When Dynaline 3 is controlled by a wall thermostat, the sequence of 

operation is the same as with built-in thermostat control; however, 

the temperature setting and system functions are selected at the 

wall thermostat.

To Shut Down for an Extended Period of Time

1. Move selector on thermostat to “STOP” or “OFF” position.

2. Close manual shut-off valve.

Summary of Contents for DYNALINE DL3-0712

Page 1: ...ls Motels Apartments and Senior Housing Four BTU h Capacities 12 20 MBTU Gas Heat Low Heating Amp Draw R 410A Refrigerant ARCHITECT S AND ENGINEER S MANUAL A Combination Gas Heating Electric Cooling S...

Page 2: ...he outside atmosphere Solid state electronic hot surface ignition HSI with no open flame is the modern alternative to pilot lights HSI increases energy conservation while ensuring safety Easy to Insta...

Page 3: ...g Tips 33 Accessory Description Review 34 Dynaline 3 Airflow 35 Suburban Limited Warranty 36 37 Dynaline 3 PTAC Features and Benefits 38 39 Hotels Motels Individual room control Energy management inte...

Page 4: ...or each specific locale Utilizing BIN Hour temperature data the following table provides representative examples of costs to operate one PTAC for one year Suburban will gladly prepare a BIN Hour Cost...

Page 5: ...er year at the mid point temperature specific to a geographical location The BIN hours are derived from historical weather data For example at a location with 7 023 heating BIN hours such as Syracuse...

Page 6: ...g infiltration of air water and contaminants into the conditioned area Electrical components Located on the indoor side of the wall they are protected from the weather and easily accessed for service...

Page 7: ...rd design provides means of lock ing out A C compressor when standby power generator is operating Electronic control board has 24V input terminals to receive lock out signal Room air discharge Attract...

Page 8: ...andem 15 amp 6 15 R Total amps cooling heating 7 5 1 2 5 1 1 0 3 8 1 0 3 3 1 0 Total watts cooling heating 1550 260 1125 150 855 150 675 150 Compressor Type Hermetic Rotary Refrigerant type HCFC R410...

Page 9: ...ressor from external vibration The system shall include copper aluminum condenser and evaporator coils with capillary refrigerant control Air flow system consists of a two speed room air motor for Hi...

Page 10: ...ructed of 20 gauge galvanized steel with a protective baked on enamel finish similar to the wall case GAS TYPE Natural gas units shall be equipped with a gas valve having a built in regulator set to o...

Page 11: ...unit should be installed where it can effectively circulate air into the room Generally the best location is midway along the wall and away from a stairwell or other opening Unit must not be located...

Page 12: ...a location inspect the wall and floor areas to determine that there are no hidden electrical wires piping tubing ducts girders wall studs etc that might interfere with the proper installation and safe...

Page 13: ...4 slope to the outside Do not slope toward front To avoid water damage to the wall do not put holes through the bottom of the wall sleeve NOTE If the unit is to be mounted flush with the exterior wall...

Page 14: ...Remote thermostat Dynaline 3 chassis are supplied for standard built in control To convert the standard chassis to function with remote thermostat connect the thermostat wiring according to thermosta...

Page 15: ...EVE BOTTOM REAR GRILLE CAULK AROUND WALL SLEEVE SURFACE OF FINISHED EXTERIOR WALL 3 MIN 2 1 Y X Y 14 X 3 4 1 4 1 4 1 4 SURFACE OF FINISHED FLOOR OR TOP OF CARPET SLOPE DOWN TO THE OUTSIDE SURFACE OF F...

Page 16: ...Suburban Dynaline 3 A E Manual 12 2016 Rev 1 16 Figure 12...

Page 17: ...8 520 1 050 1 600 20 92 190 350 730 1 100 30 73 152 285 590 890 40 63 130 245 500 760 50 56 115 215 440 670 60 50 105 195 400 610 70 46 96 180 370 560 80 43 90 170 350 530 90 40 84 160 320 490 100 38...

Page 18: ...14 4 Using the two 2 8 32 x 1 2 self tapping screws provided secure hi ear elbow as illustrated See C Figure 14 5 Insert gas inlet tube assembly See D Figure 14 through bushing in firewall NOTE The sh...

Page 19: ...for air discharge to the right but can easily be converted for discharge to the left The adaptor is 43 1 4 long with female connection The extension is 43 1 4 long with 1 male tapered flange If you w...

Page 20: ...tor and collar assembly into position on the unit Make sure the adaptor is resting on the adaptor brackets adjust brackets as needed 7 Locate the hole in the adaptor bracket and mark the underside of...

Page 21: ...daptor and collar assembly from the unit At the two locations marked on the adaptor in Step 8 drill a 7 64 diameter hole 2 places 10 Install adaptor and collar assembly on unit as illustrated and secu...

Page 22: ...rolled by a toggle switch or other means in a control panel field supplied The units remain de energized until the room becomes occupied at which time the desk attendant can energize them The standard...

Page 23: ...les of exterior grilles are available to complement building aesthetics Aluminum Grille Unpainted grille of stamped clear anodized aluminum Protects the outdoor fan coil and vent cap assembly Designed...

Page 24: ...as in the event of a diaphragm rupture Gas escapement is limited within ANSI standard levels Multipurpose mounting internal or external For best performance and quick response mount in upright positi...

Page 25: ...l Electrical Code ANSI NFPA No 70 in Canada with the latest edition of ETL C22 1 Canadian Electrical Code Figure 25 To convert the standard chassis to function with remote thermostat connect the therm...

Page 26: ...Suburban Dynaline 3 A E Manual 12 2016 Rev 1 26 Figure 26 Ladder Diagram 208 230 V A C...

Page 27: ...Suburban Dynaline 3 A E Manual 12 2016 Rev 1 27 Figure 27 Schematic 277 V A C...

Page 28: ...Suburban Dynaline 3 A E Manual 12 2016 Rev 1 28 Figure 28 Ladder Diagram 277 V A C...

Page 29: ...ency power generator without forfeiting zone temperature control on the heating cycle Dynaline 3 incorporates an A C compressor lock out capability This feature allows the compressor circuit to be loc...

Page 30: ...ust gases through the unit s vent system is obstructed creating an unsafe condition If the limit switch is determined to be defective it must be replaced Never attempt to repair it and never shunt the...

Page 31: ...air motor causes the diaphragm in the pressure switch to move closing the contacts This completes the electrical circuit to the input of the module board and a 10 second warm up period for the glo ba...

Page 32: ...temperature rise the switch will close and the compressor will again come on provided that the thermostat is still calling for cooling NOTE Dynaline 3 has a built in 5 minute delay between compressor...

Page 33: ...rise the switch will close and the compressor will again come on provided that the thermostat is still calling for cooling NOTE Dynaline 3 has a built in 5 minute delay between compressor cycles Anyt...

Page 34: ...tor Air Discharge Lateral Connector 43 Air Discharge Lateral Extension 43 Rear Gas Connection Kit Field Installed 2 PSIG Regulator Leveling Legs Set of 2 each Decor Base Panel conceals gas electric co...

Page 35: ...r either horizontally or vertically The grille is installed from the factory to deliver horizontal air flow To change the airflow to vertical simply remove the grille and reinstall in the opposite pos...

Page 36: ...on diagnosing shipping or handling THIS WARRANTY APPLIES ONLY TO THE PRODUCT IN ITS ORIGINAL INSTALLATION LOCATION AND IS VOIDED IF THE PRODUCT IS REINSTALLED ELSEWHERE FOUR YEAR LIMITED WARRANTY ON H...

Page 37: ...y costs or increases in such costs from any reason whatsoever 10 Suburban products whose serial number has been altered defaced or removed 11 Suburban products installed or warranty claims originating...

Page 38: ...ting backed by a 5 year limited warranty Copper and Aluminum Evaporator and Condenser Coils For longer life and ease of repair Coils use seamless copper tubing mechanically expanded into aluminum plat...

Page 39: ...t lights Gas is conserved and safety is ensured Room Air Discharge An attractive durable grille constructed of extruded aluminum directs air laterally Return Air Filter No tools are needed to install...

Page 40: ...nty statement can be found in each product s Installation Operation Manual on our website As part of the Suburban continuous improvement program specifications are subject to change without notice P O...

Reviews: