Suburban Dynaline 3 A&E Manual 12/2016 Rev.1

8

SPECIFICATIONS

DYNALINE

 3 SERIES

General Data

DL3-1622 DL3-1220 DL3-091 DL3-0712

Rated heating input (BTU/h)

20,000

18,000

12,000

12,000

Rated heating output (BTU/h)

16,000

14,580

9,840

9,840

Steady state efficiency

80%

81%

82%

82%

Rated cooling capacity (BTU/h)

15,000

11,500

9,500

7,600

Sensible/Latent cooling

65/35

65/35

69/31

65/35

EER

9.5

10.4

11.2

11.6

Rated air flow: fan only (CFM)

Hi cool/low cool (CFM)

Hi heat/low heat (CFM)

340

400/330

420/340

300

390/300

410/300

260

300/250

320/260

260

300/250

320/260

Weight (Lbs.)

185

180

180

180

Cabinet Color

Champagne Beige

  Minimum Installation Clearances

Outside:*

Rear to nearest obstruction

Top, sides to nearest 

      obstruction 

Centerline vent to window

3 feet

0

9"

3 feet

0

9"

3 feet

0

9"

3 feet

0

9"

Inside:

Front to nearest obstruction

Sides to nearest obstruction

Bottom to floor

(for return air)

Cabinet top to ceiling

12"**

1"

0

12"

12"**

1"

0

12"

12"**

1"

0

12"

12"**

1"

0

12"

Clearance to ground should be noted (see installation manual).

**

 Obstruction must be removable for service of unit.

  Electrical Data

Volts/Phase/Cycle

208/230-1-60

Min. wire size (Copper)

#14 AWG

#14 AWG

#14 AWG

#14 AWG

Protection-Fused

2-15 amp

2-15 amp

2-15 amp

2-15 amp

Protection-Circuit (HACR type)

Dual - 15 amp

Unit Plug:       

Amps

NEMA Rating

15 amp

6-15 P

15 amp

6-15 P

15 amp

6-15 P

15 amp

6-15 P

Receptacle:

Type

Amps

NEMA Rating

Tandem

15 amp

6-15 R

Tandem

15 amp

6-15 R

Tandem

15 amp

6-15 R

Tandem

15 amp

6-15 R

Total amps cooling/heating

7.5/1.2

5.1/1.0

3.8/1.0

3.3/1.0

Total watts cooling/heating

1550/260

1125/150

855/150

675/150

Compressor

Type

Hermetic Rotary

Refrigerant type (HCFC)

R410-A

R410-A

R410-A

R410-A

Refrigerant charge

36 oz.

32 oz.

26 oz.

28 oz.

Rated Load amps

6.6

5.1

3.9

2.9

Locked rotor Amps

32

25

22

15

Rated capacity (BTU/h)

14,100

10,300

8,050

6,600

Compressor lock-out relay

(Normally closed 24V) 

5VA enrush - 4V constant

Specifications subject to change without notice.

Condenser Fan

DL3-1622 DL3-1220 DL3-091 DL3-0712

Fan blade diameter

12"

12"

12"

12"

Number of blades

4

4

4

4

Pitch

25º

25º

25º

25º

Condenser fan motor RPM

1,500

1,500

1,500

1,500

Full load amps

0.5

0.5

0.5

0.5

  Condenser Coil

Type

Copper/Aluminum

Coil Area

364 sq. inches

Rows

3

3

3

3

Fins per inch

13

13

12

12

  Evaporator Coil

Type

Copper/Aluminum

Coil Area

260 sq. in. 260 sq. in. 234 sq. in.

234 sq. in.

Rows

3

3

3

3

Fins per inch

11

11

11

11

Refrigerant metering

Capillary

Room Air Fan Motor

Speed

2

2

2

2

RPM high/low

1500/1250 1520/1400 1260/1130

1260/1130

Full load amps

0.7

0.5

0.3

0.3

Min. wire size (60º copper)

#18 AWG

#18 AWG

#18 AWG

#18 AWG

  Gas Controls and General Data

Gas (specify)

Natural or LP

Burners

1

1

1

1

Ignition system: Solid-state

Hot surface

High limit (fixed)

220º

220º

220º

220º

Blocked flue switch

205º

200º

200º

200º

Gas connection size

3/8" IPS

3/8" IPS

3/8" IPS

3/8" IPS

Gas connection

(LH) front or rear

 Blower/Evaporator

Wheel diameter

4.53"

4.53"

4.375"

4.375"

Wheel width

26"

26"

26"

26"

Air vent-manual

70 CFM

70 CFM

70 CFM

70 CFM

Required filter (1 each)

8-1/4"x30-3/4" 6"x30-3/4"

6"x30-3/4"

6"x30-3/4"

Filter type

Electrostatic/washable media

Summary of Contents for DYNALINE DL3-0712

Page 1: ...ls Motels Apartments and Senior Housing Four BTU h Capacities 12 20 MBTU Gas Heat Low Heating Amp Draw R 410A Refrigerant ARCHITECT S AND ENGINEER S MANUAL A Combination Gas Heating Electric Cooling S...

Page 2: ...he outside atmosphere Solid state electronic hot surface ignition HSI with no open flame is the modern alternative to pilot lights HSI increases energy conservation while ensuring safety Easy to Insta...

Page 3: ...g Tips 33 Accessory Description Review 34 Dynaline 3 Airflow 35 Suburban Limited Warranty 36 37 Dynaline 3 PTAC Features and Benefits 38 39 Hotels Motels Individual room control Energy management inte...

Page 4: ...or each specific locale Utilizing BIN Hour temperature data the following table provides representative examples of costs to operate one PTAC for one year Suburban will gladly prepare a BIN Hour Cost...

Page 5: ...er year at the mid point temperature specific to a geographical location The BIN hours are derived from historical weather data For example at a location with 7 023 heating BIN hours such as Syracuse...

Page 6: ...g infiltration of air water and contaminants into the conditioned area Electrical components Located on the indoor side of the wall they are protected from the weather and easily accessed for service...

Page 7: ...rd design provides means of lock ing out A C compressor when standby power generator is operating Electronic control board has 24V input terminals to receive lock out signal Room air discharge Attract...

Page 8: ...andem 15 amp 6 15 R Total amps cooling heating 7 5 1 2 5 1 1 0 3 8 1 0 3 3 1 0 Total watts cooling heating 1550 260 1125 150 855 150 675 150 Compressor Type Hermetic Rotary Refrigerant type HCFC R410...

Page 9: ...ressor from external vibration The system shall include copper aluminum condenser and evaporator coils with capillary refrigerant control Air flow system consists of a two speed room air motor for Hi...

Page 10: ...ructed of 20 gauge galvanized steel with a protective baked on enamel finish similar to the wall case GAS TYPE Natural gas units shall be equipped with a gas valve having a built in regulator set to o...

Page 11: ...unit should be installed where it can effectively circulate air into the room Generally the best location is midway along the wall and away from a stairwell or other opening Unit must not be located...

Page 12: ...a location inspect the wall and floor areas to determine that there are no hidden electrical wires piping tubing ducts girders wall studs etc that might interfere with the proper installation and safe...

Page 13: ...4 slope to the outside Do not slope toward front To avoid water damage to the wall do not put holes through the bottom of the wall sleeve NOTE If the unit is to be mounted flush with the exterior wall...

Page 14: ...Remote thermostat Dynaline 3 chassis are supplied for standard built in control To convert the standard chassis to function with remote thermostat connect the thermostat wiring according to thermosta...

Page 15: ...EVE BOTTOM REAR GRILLE CAULK AROUND WALL SLEEVE SURFACE OF FINISHED EXTERIOR WALL 3 MIN 2 1 Y X Y 14 X 3 4 1 4 1 4 1 4 SURFACE OF FINISHED FLOOR OR TOP OF CARPET SLOPE DOWN TO THE OUTSIDE SURFACE OF F...

Page 16: ...Suburban Dynaline 3 A E Manual 12 2016 Rev 1 16 Figure 12...

Page 17: ...8 520 1 050 1 600 20 92 190 350 730 1 100 30 73 152 285 590 890 40 63 130 245 500 760 50 56 115 215 440 670 60 50 105 195 400 610 70 46 96 180 370 560 80 43 90 170 350 530 90 40 84 160 320 490 100 38...

Page 18: ...14 4 Using the two 2 8 32 x 1 2 self tapping screws provided secure hi ear elbow as illustrated See C Figure 14 5 Insert gas inlet tube assembly See D Figure 14 through bushing in firewall NOTE The sh...

Page 19: ...for air discharge to the right but can easily be converted for discharge to the left The adaptor is 43 1 4 long with female connection The extension is 43 1 4 long with 1 male tapered flange If you w...

Page 20: ...tor and collar assembly into position on the unit Make sure the adaptor is resting on the adaptor brackets adjust brackets as needed 7 Locate the hole in the adaptor bracket and mark the underside of...

Page 21: ...daptor and collar assembly from the unit At the two locations marked on the adaptor in Step 8 drill a 7 64 diameter hole 2 places 10 Install adaptor and collar assembly on unit as illustrated and secu...

Page 22: ...rolled by a toggle switch or other means in a control panel field supplied The units remain de energized until the room becomes occupied at which time the desk attendant can energize them The standard...

Page 23: ...les of exterior grilles are available to complement building aesthetics Aluminum Grille Unpainted grille of stamped clear anodized aluminum Protects the outdoor fan coil and vent cap assembly Designed...

Page 24: ...as in the event of a diaphragm rupture Gas escapement is limited within ANSI standard levels Multipurpose mounting internal or external For best performance and quick response mount in upright positi...

Page 25: ...l Electrical Code ANSI NFPA No 70 in Canada with the latest edition of ETL C22 1 Canadian Electrical Code Figure 25 To convert the standard chassis to function with remote thermostat connect the therm...

Page 26: ...Suburban Dynaline 3 A E Manual 12 2016 Rev 1 26 Figure 26 Ladder Diagram 208 230 V A C...

Page 27: ...Suburban Dynaline 3 A E Manual 12 2016 Rev 1 27 Figure 27 Schematic 277 V A C...

Page 28: ...Suburban Dynaline 3 A E Manual 12 2016 Rev 1 28 Figure 28 Ladder Diagram 277 V A C...

Page 29: ...ency power generator without forfeiting zone temperature control on the heating cycle Dynaline 3 incorporates an A C compressor lock out capability This feature allows the compressor circuit to be loc...

Page 30: ...ust gases through the unit s vent system is obstructed creating an unsafe condition If the limit switch is determined to be defective it must be replaced Never attempt to repair it and never shunt the...

Page 31: ...air motor causes the diaphragm in the pressure switch to move closing the contacts This completes the electrical circuit to the input of the module board and a 10 second warm up period for the glo ba...

Page 32: ...temperature rise the switch will close and the compressor will again come on provided that the thermostat is still calling for cooling NOTE Dynaline 3 has a built in 5 minute delay between compressor...

Page 33: ...rise the switch will close and the compressor will again come on provided that the thermostat is still calling for cooling NOTE Dynaline 3 has a built in 5 minute delay between compressor cycles Anyt...

Page 34: ...tor Air Discharge Lateral Connector 43 Air Discharge Lateral Extension 43 Rear Gas Connection Kit Field Installed 2 PSIG Regulator Leveling Legs Set of 2 each Decor Base Panel conceals gas electric co...

Page 35: ...r either horizontally or vertically The grille is installed from the factory to deliver horizontal air flow To change the airflow to vertical simply remove the grille and reinstall in the opposite pos...

Page 36: ...on diagnosing shipping or handling THIS WARRANTY APPLIES ONLY TO THE PRODUCT IN ITS ORIGINAL INSTALLATION LOCATION AND IS VOIDED IF THE PRODUCT IS REINSTALLED ELSEWHERE FOUR YEAR LIMITED WARRANTY ON H...

Page 37: ...y costs or increases in such costs from any reason whatsoever 10 Suburban products whose serial number has been altered defaced or removed 11 Suburban products installed or warranty claims originating...

Page 38: ...ting backed by a 5 year limited warranty Copper and Aluminum Evaporator and Condenser Coils For longer life and ease of repair Coils use seamless copper tubing mechanically expanded into aluminum plat...

Page 39: ...t lights Gas is conserved and safety is ensured Room Air Discharge An attractive durable grille constructed of extruded aluminum directs air laterally Return Air Filter No tools are needed to install...

Page 40: ...nty statement can be found in each product s Installation Operation Manual on our website As part of the Suburban continuous improvement program specifications are subject to change without notice P O...

Reviews: