Page 121
Troubleshooting Guides
Integrated (
Integrated (
700-
700-
2) Series
2) Series
8-15
#
3756780
- Revision D - July, 2005
PROBLEM
POSSIBLE CAUSE
TEST / ACTION
(Continued)
D. Warm Refrigerator
Temperatures without
“SERVICE” Flashing
(See Pointers on previous page)
Lights ON with Door/ Drawers Closed
a. Top hinge cover missing, not depress-
ing light switch
b. Faulty light switch
Evaporator Fan fault
a. Top hinge cover missing fan switch
b. Fan blade obstructed or out of position
c. Faulty fan switch
(
NOTE:
A compressor must be running)
d. Evaporator. fan motor disconnected
e. Evaporator fan motor defective
(
NOTE:
Compressor must be running)
Compartment or Evaporator Thermistor
Misread
Evaporator Heavily Frosted
a. Door or drawer ajar
b. Evaporator fan fault
c. Thermistor misread
Power to Compressor Fault
NOTE:
For 700TF/I-2V, see Error Code
Troubleshooting Guide
Sealed System Fault
•
Sealed System Leak
•
Sealed System Restriction
•
Inefficient Compressor
a. Replace hinge cover.
b. Check operation of light switches, lights off
when switch is depressed. Replace switch if
defective.
(
NOTE:
there are two light switch-
es in the drawer area)
a. Replace hinge cover.
b. Move obstruction or reposition blade.
c. Check for 115V AC to fan switch, depress
fan switch and check for 115V AC from fan
switch. Replace switch if defective.
(
NOTE:
there are two fan switches in the
drawer area)
d. Check electrical connections of motor.
Reconnect / repair bad connections.
e. Check for 115V AC at fan motor with fan
switch depressed. Replace motor if defec-
tive.
Check resistance of refrigerator compart-
ment and evaporator thermistors for 30,000
to 33,000 ohms at 32°F. Replace thermistor
if defective.
a. See Door or Drawer Ajar on previous page.
b. See Evaporator Fan Fault above.
c. See Compartment & Evaporator Thermistor
Misread above.
Check for 115V AC at E7 and/or E6 on con-
trol board. Replace control board if defec-
tive.