7
}
© STULZ GmbH – all rights reserved EN/11.2018/G67C
wib8000 original instructions
Bus activity:
Bus 1, red LED when sending data,
Bus 2, green LED when receiving data, but also when data is
sent, as the WIB checks outgoing data.
Network: Connection established, when LED illuminates
Network: Data transmission, when LED illuminates
State indication
illuminates:
WIB ready
blinks:
Data is being saved, please
wait.
Alarm indication
illuminates:
Alarm on at least one controller
blinks:
internal WIB alarm (e.g.: e-mail cannot be sent),
such an alarm is shown in the eventlog, but not in the
alarm window
Function of LEds
• Datamanagementofupto2x32Stulzcontrollers(A/Cunits)
• standaloneunit
• nodisplayorkeyboard,configurationandserviceexclusivelywithaPCvianetwork
• independentrealtimeclock.
• ThesoftwareissavedinaFlashROM.NewsoftwarecanbedownloadedfromanotebookorPCwithoutthe
need of changing hardware.
• LED’sshowcurrentbusactivityandoperatingstateoftheboard.
• TheterminationresistorsfortheRS485bussesareactivatedbyinternalswitches.