wib8000 original instructions
Zone
Here you can set the time between update procedures for the WIB zone. During an update procedure the
zone values (temperature/humidity) are calculated and, if necessary, units are switched on/off based on
these values. This procedure is also carried out after each alarm query (query interval adjustable in menu "web
interface/alarm").
The time-controlled sequencing is not affected by this parameter.
Note:
For heavily loaded systems (continuous query via SNMP for slow connection of units and at the same time
maximum unit number), a low refresh time (less than 3 seconds) can cause problems with the time-controlled
sequencing.
HTTP
You can have displayed a freely selectable logo in the top right corner of each page. In the choice box "source"
you can enter the path, which describes the location where the logo is saved. The memory location can be on
a server and must be indicated by a link as "http://..." then. By clicking on the logo the adjustable hyperlink is
executed.
User
Setting the "Timeout" you determine the delay after which you are automatically logged out when the browser
has been closed.
Password
In this menu you can define the passwords for different authorizations. Password 1 allows the access to the
highest authorization level. Password 2 allows except the modifications of setpoints only the display of all
parameters of the menu levels "Info" and "Operate". Password 3 includes the authorization to read all parame-
ters of the menu levels "Info" and "Operate".