20
EN/11.2018/G67C © STULZ GmbH – all rights reserved
wib8000 original instructions
The names of the units found are generated automatically by adding the bus number to the expression "Unit"
in the adjusted standard language and after the insertion of a hyphen the global address of the unit. For
C7000 IO controllers the unit name saved in the controller, if it is not the default setting "unit name", will be
taken.
So the unit names are displayed in the bus and zone view as represented below.
This name can be modified in the menu "Config/Web interface" for each unit.
Manual configuration of units within the bus configuration
Under certain circumstances an automatic unit detection by
the "scan" function in the bus menu is not possible. This is the
case if a unit/controller can not be provided with voltage at
the time.
By menu item "create unit" in the menu "Web Interface/bus"
you have the possibility to manually create units.
By menu item "delete unit" in the same menu you can remove
a unit from the bus configuration, without cutting the bus
wiring. Such could be the case if you want to operate the
A/C unit temporarily as an individual A/C unit e.g. for test
purposes.
Up to 20 freely selectable parameters can be displayed for each unit in the bus or zone overview. These
parameters can be defined in the menu "config/web interface". The size of the unit blocks conforms to the
largest block in a line.
cache holding period has expired. Taking into account the bus performance (number of units, connection type
Ebus via C7000AT, response times of units), the pre-fetch period may not be set too small, because otherwise
the bus queue will be overloaded. In this case not all data points can be read.