24
EN/11.2018/G67C © STULZ GmbH – all rights reserved
wib8000 original instructions
In the lower part of the menu, there are displayed parameters which can be adjusted individually for each unit
to use the WIB zone functionality.
These parameters enclose the assignment to a zone (by the assignment of a unit to a zone the zone is creat-
ed.), the determination of the position within the sequencing, the definition of the operating state at the begin-
ning of the sequencing (on/off) and eventually the parameters for an overload start.
Choice box: Zone
To avoid problems which result from assigning a unit to different zones (WIB zone and IOC zone), the following
check is carried out. If the parameter "IOC Zone" in the menu "Info/IOC zone" (data point myZone) is different
from "0", you can not introduce a value for the WIB Zone in menu "Config/Web Interface". If an IOC, which has
already been assigned to a WIB zone before, is added to an IOC zone (by IOC or AT), this IOC is removed from
the WIB zone as soon as the WIB detects it. An IOC zone can only be configured for C7000 controllers.
Choice box: Position
In this box you can set the unit order for the sequencing. The sequencing runs in an ascending numerical
order. Each position number may only be assigned once.
Before this setting existed, the sequencing order was determined by the global address (also across the bus).
Now you can define an order, independantly on the global address, which corresponds for example to the local
installation of units.
Choice box: Stop datapoint
For C7000IOC controllers you can set a data point, which the WIB also uses (besides the commutation point
or elapsed interval or valid alarm) in the course of the sequencing to switch off a C7000IOC.
Two settings are available "BMS stop 1" and "BMS stop 2".
Zone configuration for each unit in menu "Config/Web interface"
Possibility to introduce a value
depends on value in Info/IOC
Zone