7. Troubleshooting
7.1 Problems with the connection via SNMP
1. Reachability
•Checkbythe"ping"command,whethertheWIBmodulecanbereachedviaEthernet.
•Checkwhetherthe
is set as "enabled". (see page 17)
•TesttheconnectionusingthefreelyavailableHilisoftMIB-Browser.ThefollowingsOIDsaresuitableforthe
function test of the connection.
OID:1.3.6.1.2.1.1.1.0 --> Stulz GmbH Klimatechnik WIB 8000 // sysDescr
OID:1.3.6.1.2.1.1.2.0 --> 1.3.6.1.4.1.29492.10 // sysObjectID
OID:1.3.6.1.2.1.1.5.0 --> WIB 8000 SNMP Interface // sysName
OID:1.3.6.1.2.1.1.6.0 --> aircondition // sysLocation
2. Speed
(Timeout, Cache holding time and Pre-fetch period) on page 19.
As many values do not change so often, you can set a bigger cache holding time.
•IftheWIBmoduleisconnectedwiththeA/Cunits(C7000IOCs)byaC7000AT,thedatarequestisslower
than if it is connected with the C7000IOC and the A/C unit by an E-Bus board.
•Use"GET"commandsfortherequestofdatapoints.
•Avoidthe"WALK"command.
Theavailabledatapointscanbetakenfromthefile"StulzWIB8000_v2xx_oidlist.pdf"whichcanbedown-
loaded from the E-Stulz area.