Varan 1.14, 1.20
Changes in models reserved.
Dimensions not binding!
14
Situation 1 Chimney Connection Varan 1.14
Connection To The Flue
Montage Possibilities
- Situation 1: The boiler is connected to a standard chimney
(stone-walled or metal), which has a fundament and a whole
cross section of the fundament plate to the upper end point.
- Situation 2: The boiler is connected to a stainless steel flue
which is mounted to the facade.
Installation
Situation 1:
- The chimney uses ceramic or metal pipes of circular cross-
section of 130 mm diameter. The flue pipe must be insulated.
- If the chimney already exists and is of square cross-section,
then the minimum dimension of the intersection is
130x130 mm.
- It is not allowed to use one chimney for connecting multiple
boilers.
- It is not allowed to use the air vents like a chimney.
- The top of the chimney must be protected with a chimney
cap due for the impact of rain and winds.
Distance of chimney to cap is 200 mm.
- The chimney should come out above the roof according to
the recommendations in the image on page 17.
If other objects are near the chimney, take this into account
and increase the height of chimney.
- The chimney must have a connection to extract condensation
and an inspection door. The door should always be sealed
well during the operation.
Air supply connection Exhaust connection