Display message
F7
F l u e t e m p t o o h i g h
p u m p o n
9 9 9 , 5 h r s
Reason
Flue gas temp. exceeded 3 times limitation value within a certain
period.
Cause:
Heat exchanger polluted and not able to transfer enough heat to system water.
Corrective action:
Check and clean heat exchanger.
Cause:
Bad flue gas sensor or sensor connection (partly shorted).
Corrective action:
The sensor is of the type NTC. This means if the temperature rises the resistance lowers.
A partly shorted sensor will drop its resistance and therefore 'measure' a raise in tem-
perature when actually there is none.
Check for moist in the sensor connections or replace sensor.
Cause:
There is no water in the unit while firing.
Corrective action:
This is an unlikely situation while all the safeties for checking the water presence didn't
detect anything. Only a lot of air in the system/unit (under pressure) can cause the water
pressure switch to switch while no water is present. Also the water leak detection
did not react. Bleed all air from the unit so the heat from combustion can be transferred to
the water and won't leave through the flue system.
Cause:
Heat exchanger failure.
Corrective action:
This is an unlikely situation but when there is severe damage to the heat exchanger, the
combustion product will not be able to transfer all heat to the system water. The heat that
is not transferred will convert to an increased flue gas temperature.
Display message
F8
F a i l e d b u r n e r s t a r t
p u m p o n
9 9 9 , 5 h r s
Reason
Boiler not operational after 4 starting attempts.
Cause:
No spark.
Corrective action:
Check the igniter/ignition electrode and replace/clean it if necessary.
Check the state of the ceramic insulator. A small crack can prevent the spark to form at
the end of the electrode.
Check the distance between the electrode pin, earth pin and burner.
Check the state of the ignition cable and replace it if necessary.
Check the state of the earth wire/connection of the igniter and replace it if necessary.
Check the state of the sparkplug cap and replace it if necessary.
Check power supply. Voltage must be 230 Vac nom.
Check for proper electrical grounding of unit.
Bad ignition transformer. Replace the burner control of the unit.
F8
→
Summary of Contents for S-CB Px 120
Page 2: ...S CB Px 120 Manual 2 ...
Page 6: ...S CB Px 120 Manual 6 ...
Page 33: ...S CB Px 120 Manual 33 9 4 Electrical schematics ...
Page 34: ...S CB Px 120 Manual 34 ...
Page 111: ...S CB Px 120 Manual 111 ...
Page 115: ...S CB Px 120 Manual 115 weather dependent control 49 73 ...
Page 116: ......
Page 117: ......