S-CB Px 120 Manual
59
10.16.
Setting the parameters with the display menu
The functions of the controller are embedded in de electronics by means of parameters. The values and settings
hereof can be programmed by a skilled and trained service engineer with the help of a computer (laptop), the
correct software and an interface cable. A selection of these parameters can be programmed at the control panel
of the unit itself, without the use of a computer.
The following table gives a list of all parameters that can be programmed at the control panel without the use of a
laptop/computer. NOTICE: Only the password for level 1 is issued in this manual. “More advanced” parameters
need to be programmed by a skilled and trained service engineer with access to level 2.
When ‘Modify = no’, the parameter can only be programmed at level 2
PASSWORD:
1342
MENU
PARA-
METER
DESCRIPTION
UNITS
TEXT DISPLAY
LEVEL 1
Modify
HE
A
T
ING
A
1
P5BE Step modulation (1=on 0=off)
-
S t e p m o d u l
no
2
P5AO Blocking offset flow temperature control
°C
H E s O f f 1 3
yes
3
P5AP Proportional range temperature control
°C
H E s P r b 1 3
no
4
P5AL Hysteresis CH Flow temperature control
°C
H E s c D i f 1 3
yes
5
P2IC Integration time temperature control
s
H E s I n t 1 3
no
6
P2MI Blocking offset System CH temperature control
°C
H E
c O f f 3
yes
7
P2MJ Proportional range System CH temperature control
°C
H E
c P r b 3
no
8
P2MK Integration time CH temperature control
s
H E
c I n t 3
no
9
P5AB Timer Contact (1=on)
-
T i m e r C o n t
yes
DHW
B
1
P4AB DHW Pump Config 0=Pump 1=TWV
-
D H i p m p / t w v
yes
2
P5CB Flow temperature DHW tank low
°C
D H i f l o w L O
yes
3
P5CK Flow temperature DHW tank hi
°C
D H i f l o w H I
yes
4
P5CL Low Flow temperature time DHW
min
D H i L O t i m e
yes
5
P5CD Legionella temperature
°C
L e g i o t e m p
no
6
P5CI Legionella hyst DHW tank temperature
°C
L e g i o h y s t
no
7
P5CJ Legionella hold time (0=off)
min
L e g i o h o l d
no
8
P2KI CH interrupt by Legionella (0=yes)(1=no)
-
L e g i o i n t r
no
9
P2LC Regulation temperature offset DHWd
°C
D H d s c O f f 2
yes
A
P2MN Proportional range DHWd modulation
°C
D H d s c P r b 2 3
no
B
P2LD Regulation temperature hysteresis DHWd
°C
D H d s c D i f 2
yes
C
P2MO integration time DHWd modulation
s
D H d s c I n t 2 3
no
D
P2ML Sys temp blocking offset DHW tank
°C
D H d s c O f f 3
yes
E
P2MM Sys temp blocking hysteresis DHW tank
°C
D H d s c D i f 3
yes
F
P5CA Hysteresis DHW tank temperature
°C
D H i s c D i f 4
yes
G
P2KH Gradient heat demand detect DHW tank temperature
°C
D H i d e t g r a d
yes
CA
S
CA
DE
C
1
P2MA Max number extra boilers
-
M a x C a s c U n t
no
2
P5DA Bus address boiler
-
B u s a d r e s s
no
3
P5DC Dhw on entire cascade(0) only master(1)
-
D H i c a s / m a s
no
4
P5DE Extra Boiler output enable(1)
-
E x t r a u n i t
yes
5
P5DF Cascade detection (0=standalone 1=Leader)
-
C a s S i / M a
no
6
P5BL Power off total cascade (1)
-
P w r O f f T o C a
no
7
P5DB Number of boilers with common flue 0=None
-
C o m F l u N u m
no
GE
NE
RAL
D
1
P5BB Analogue input Config (0=off 1=temp 2=power)
-
A n I n p C o n
yes
2
P5AI Minimum Temperature 0-10V input
°C
0 - 1 0 M i n T m p
yes
3
P5BI Altitude (in amounts of 100 ft.)
100 ft
A l t * 1 0 0 f t
yes
4
P2LK Max cooling time
min
M a x C o o l T i m
yes
5
P5BJ Temperature display 1=on
-
T e m p O n D i s p
yes
6
P4AA DHW 0=off 1=Indirect 2=Direct
-
D H W 1 = i 2 = d
no
7
P4AD pressure 0=off 1=sensor and 2=switch
-
c o n f i g
no
8
P4BD Gas type values 0-2
-
g a s t y p e
no
9
P4BE Soft start type values 0-2
-
c o n f i g
no
A
P5BN Pump modes 0-3
-
c o n f i g
no
For extensive explanation see Ch. 11: ‘Controlling options and settings’, page 70 ff.
IMPORTANT:
Do not change the parameters P2LC, P2LD, P2ML, P2MM and P5BI; they are present in the con-
troller for different purposes than CH control. Changing these parameters may affect boiler operation negatively
.
Parameter s concise explanation see next pages
→
Summary of Contents for S-CB Px 120
Page 2: ...S CB Px 120 Manual 2 ...
Page 6: ...S CB Px 120 Manual 6 ...
Page 33: ...S CB Px 120 Manual 33 9 4 Electrical schematics ...
Page 34: ...S CB Px 120 Manual 34 ...
Page 111: ...S CB Px 120 Manual 111 ...
Page 115: ...S CB Px 120 Manual 115 weather dependent control 49 73 ...
Page 116: ......
Page 117: ......