S-CB Px 120 Manual
61
Menu A: Heating
A 7 H E
c P r b 3
2 5 ° C
Select the cascaded boilers supply temperature control.
This parameter is the proportional range of the selected CH
supply temperature of EACH boiler of the total cascade and of
the external (cascade) sensor.
Menu A: Heating
A 8 H E
c l n t 3
8 0 S e c
Select the cascaded boilers supply temperature control.
This parameter is the integration time of the selected CH sup-
ply temperature of EACH boiler of the total cascade and of
the external (cascade) sensor.
Menu A: Heating
A 9 T i m e r C o n t
0
Function to activate "external time controller":
0 = Off
1 = On
Connect to 13-14. Contact closed = daytime setting,
Contact open = night-time setting.
Menu B: Hot water
B 1 D H i p m p / t w v
1
Hot water function of the boiler by:
0 = pump
1 = 3-way valve
Menu B: Hot water
B 2 D H i f l o w L O
2 5 ° C
Hot water function of the boiler. This parameter is the CH
supply temperature LOW level with an indirect hot water de-
mand.
Menu B: Hot water
B 3 D H i f l o w H I
8 5 ° C
Hot water function of the boiler. This parameter is the CH
supply temperature HIGH level with an indirect hot water de-
mand.
Menu B: Hot water
B 4 D H i L O t i m e
1 M i n
Hot water function of the boiler. This parameter is the se-
lectable time period after which the boiler switches from LOW
to HIGH set point with an indirect hot water demand.
Summary of Contents for S-CB Px 120
Page 2: ...S CB Px 120 Manual 2 ...
Page 6: ...S CB Px 120 Manual 6 ...
Page 33: ...S CB Px 120 Manual 33 9 4 Electrical schematics ...
Page 34: ...S CB Px 120 Manual 34 ...
Page 111: ...S CB Px 120 Manual 111 ...
Page 115: ...S CB Px 120 Manual 115 weather dependent control 49 73 ...
Page 116: ......
Page 117: ......