S-CB Px 120 Manual
90
16.
FAULT CODES AND BLOCKING CODES
16.1.
Fault codes
IMPORTANT:
To avoid electric shocks, disconnect electrical supply before performing troubleshooting.
To avoid burns, allow the unit to cool before performing troubleshooting.
Be aware that a fault code is an indication that the unit or the system needs attention.
When repeatedly having faults these should not be neglected.
The first step is to check if the unit is installed according to the instructions. If not, first
make sure the installation complies with the installation manual.
Always check the fuses on the control board before replacing any major components. A
blown fuse can prevent the controller or other components from operating.
Most faults can also be caused by a bad wiring and/or connections, even if it is not spe-
cifically mentioned. With every fault it is wise to check wiring and connections (at both
ends) that connect to the safety device/component that generates the fault .
LOCK-OUT CODES:
Having a lockout means that the boiler needs a manual reset to start operating again.
When the boiler is in lockout the backlight of the display is blinking on and off.
Explanation >
9 9 9 , 5 : h r s
= time elapsed after
fault/message.
Explanation >
P u m p 1 o n
= status of the pump during fault.
Display message
F0
F l o w s e n s o r e r r o r
p u m p o n
9 9 9 , 5 h r s
Reason
Flow sensor is not detected.
Cause:
Bad wiring/connection in the flow sensor circuit.
Corrective action:
Check for loose wiring/connections in the flow sensor circuit.
Cause:
Bad temperature sensor causing a fault signal.
Corrective action:
Replace flow sensor.
Display message
F1
F l o w h i g h T e m p
p u m p o n
9 9 9 , 5 h r s
Reason
Max. flow temperature exceeds limitation (lock-out) value.
Cause:
The water flow is restricted.
Corrective action:
Check functioning of the pump.
Check/open all valves that might restrict the water flow through the unit.
Check for an external system pump that influences flow through the unit.
Check if the system resistance exceeds the spare capacity of the unit pump.
Summary of Contents for S-CB Px 120
Page 2: ...S CB Px 120 Manual 2 ...
Page 6: ...S CB Px 120 Manual 6 ...
Page 33: ...S CB Px 120 Manual 33 9 4 Electrical schematics ...
Page 34: ...S CB Px 120 Manual 34 ...
Page 111: ...S CB Px 120 Manual 111 ...
Page 115: ...S CB Px 120 Manual 115 weather dependent control 49 73 ...
Page 116: ......
Page 117: ......