HE200 - Installation and Operation Manual
35
6.3.1.1
Raised base installation of more than 8" (R value for the hearth extension not required)
The HE200 may be installed directly on the floor or on a raised combustible or non combustible base. If the
fireplace is elevated more than 8" (
B
), an R value for the hearth extension is not required and the floor
protector must extend at least 16" (41 cm) in front of the unit. However, the upper and lower angle, for the
full width of the floor protection, must be protected 2" horizontally and vertically (
E
) by a non-combustible
material. For example, a sheet metal (not included). Apart from these two corners, the sheet metal does
not have to cover the rest of the wall between the base of the fireplace and the floor.
CLEARANCES
MINIMUM
MEASUREMENT
A
84" (2134 mm)
E
2" (51 mm)
B
8" (203 mm) minimum