background image

22 

Doc653/30CV02A

 

6.3 Boiler module KM628

Lid 

closed 

    Lid 

open

6

4 3

2

1

7

5

 

 

9 8

7

6

5

3

2

1

4

Fig.6 Boiler module

Operating 

mode 

   1 

Parameter 

indication

 

K

  Stand-by  

 

 

 

 

P1 Actual/required fl ow temperature

 

q

  Automatic operation (winter position)  

 

P2 Actual/required hot water temperature

 

t

  Hot water operation (summer position) 

 

P3 Required fl ow temperature* 

 

W

  Service operation (constant load) 

 

 

P5 Actual external temperature

2  Rotary selection switch: operating mode 

 

P6 Actual fl ue gas temperature

3  Fault indicator 

 

 

 

 

P9 Actual/maximum appliance load 

4 Actual fl ow 

temperature 

   

P10 

Password

5  Error code (fl ashing)  

 

 

2  Optical bus connection for Kesslab

Operating 

status 

   3 

Reset/programming 

push 

button

 

B

  Night 

off 

    

 4 

Alarm/programming 

LED 

 

D

  Day / on operation   

 

 

5  Rotary selection switch for parameter 

 

D

  (Flashing) Burner in operation 

 

 

number selection and required setting

7 Service position 

 

 

 

 

adjusting

 

W1

  Service operation at minimum  

 

6  Output status

 

 

 

burner load (P17)     7  Actual/required parameter value

 

W2

  Service operation at maximum    

8  Error code /parameter number

 

 

 

burner load (P9)  

 

 

9  Status inputs 

 

 

 

 

 

 

 

 

* Desired load required by the  KKM if fi tted

Control functions with the lid in the closed position

With the lid in the close position and by operating the rotary selection switch, the operating mode 
can be changed to:

K

   

Standby (the boiler is out of operation and the frost protection unit is active)

q

   

Automatic operation (the boiler is in operation for central heating and hot water production 

t

   

Hot water operation (the boiler is only in operation for hot water production

W1

  Service operation  (the boiler is operating at constant minimum load set at P17)

W2

  Service operation (the boiler is operating at constant maximum load set at P9)

Information and settings if the lid is opened

With the lid open and by operating the rotary selection switch, one can access the following 10 
parameters. An arrow at the bottom of the display indicates the selected parameter and the actual 
value of the same is simultaneously displayed.

Summary of Contents for ECONOFLAME R30

Page 1: ...ILERS INSTALLATION OPERATION MAINTENANCE DOCUMENTATION STOKVIS ENERGY SYSTEMS 96R WALTON ROAD EAST MOLESEY SURREY KT8 0DL TEL 08707 707 747 FAX 08707 707 767 E MAIL info stokvisboilers com WEBSITE www...

Page 2: ...r manner whatsoever without the prior permission of Rendamax B V in writing We are engaged in a constant effort to improve our products As a result of this process the products may deviate slightly fr...

Page 3: ...ea 5 2 1 General 5 2 2 Installation 5 2 3 Ventilation 11 5 3 Connections 5 3 1 Gas connection 5 3 2 Electrical connections 5 3 3 Water connections 14 5 3 4 Flue gas outlet and air inlet 5 3 4 1 Connec...

Page 4: ...23 6 5 Setting into operation 25 6 6 Switching off the appliance 6 7 Warnings 7 Commissioning 7 1 General 7 2 Commissioning 26 8 Maintenance 27 8 1 Safety 8 2 General 8 3 Procedure 28 8 4 Cleaning the...

Page 5: ...6 17 20 30 50 Maximum water temperature of central heating system Maximum operating pressure Water content Water resistance T 20 C Excess head of the boiler pump T 20 C C bar litre kPa kPa 90 6 5 1 1...

Page 6: ...00 G R 3 4 R 3 4 R 3 4 R 3 4 R 3 4 L mm 340 405 510 560 670 L1 mm 74 90 90 90 90 W R 11 4 Rp 1 R 11 4 Rp 1 R 11 4 Rp 1 R 11 4 Rp 1 R 11 4 Rp 1 Table 2 Dimensions of the R30 We reserve the right to mak...

Page 7: ...of this documentation You can of course always obtain further information via www stokvisboilers com 1 3 This document The present documentation has been prepared with the following target groups in...

Page 8: ...the boiler is delivered fully wired fully assembled and tested Working principle and design Air is drawn in as required via a speed controlled fan The zero pressure controller of the gas valve measur...

Page 9: ...heating systems with constant ow temperature weather dependent set point adjustment low temperature condensing system external temperature control via building optimiser 0 5 Vdc 10 C 90 C below 1Vdc t...

Page 10: ...ler 11 Automatic boiler controller 21 Control panel 2 2 1 Description of principal components The boiler is made of the following components Fan 9 The fan pulls in and compresses the combustion air dr...

Page 11: ...epending on the load Condensate drain 13 The boiler is equipped with a bottle trap This bottle trap is located on the bottom side of the ap pliance and can be easily lled with water Frame 14 The frame...

Page 12: ...nised installer in accordance with applicable na tional and local standards and speci cations The installation should only be used for heating systems with a maximum water temperature of 90 C It is ex...

Page 13: ...r covered up and should be maintained in a legible condition throughout the life of the appliance Immediately replace damaged or illegible instruction and warning stickers Modi cation The appliance ma...

Page 14: ...ng the winter are in danger of freezing Drain out the water from the lling and drain valve 5 Installation 5 1 Regulations The appliance should be installed by a recognised installer in accordance with...

Page 15: ...3 1 Gas connection The gas connection should be installed by a recognised installer in accordance with applicable national and local standards and speci cations The gas connection is located on the b...

Page 16: ...es according to the EMC Directives Controls and options The boilers are equipped with a modulating control system The temperature can be controlled via a 0 5 Vdc signal for example in response to exte...

Page 17: ...olled hot water re circulation pump Pump kick function DCF receiver for internal clock optional receiver required Communication over a CAN bus Integrated relay and sensor test Can be used in stand alo...

Page 18: ...the ow and return pipes are securely xed with brackets This prevents damage and makes maintenance easier The boiler is an instantaneous boiler and is not suitable for use in open vented systems In suc...

Page 19: ...connection for the air supply is on the top of the boiler The air supply pipe should be airtight This is to prevent the suction of false air Horizontal com ponents in the air supply should be installe...

Page 20: ...is equipped with a premix burner with a fan an overpressure is created in the boiler This overpressure is suf cient to overcome the resistance of the burner the heat exchang er and the chimney The ba...

Page 21: ...Diameter in mm Pipe bend 90 R D 0 5 Pipe bend 90 R D 1 Pipe bend 45 R D 0 5 T piece R30 45 70 80 3 5 4 0 1 4 1 5 1 1 1 2 4 0 4 0 R30 65 80 90 100 4 0 4 5 4 9 1 5 1 7 1 8 1 2 1 3 1 4 4 0 4 5 5 4 R30 8...

Page 22: ...tion should not be adverse ly affected by the use of valves non return valves systems in which several boilers are connected to a common distribution pipe etc The maximum water ow is achieved at t 15...

Page 23: ...1 0 0 5 0 2 Rp 1 Rp 11 4 0 0 5 10 lgpm 0 0 5 1 1 5 2 l s 1 2 3 4 5 6 m3 h m s v 15 20 3 1 5 Wilo TOP S 25 7 Wilo TOP S 30 7 1 230 V Rp 1 Rp 11 4 2 2 2 Q H m Fig 5 Pump characteristics 5 4 1 3 Shut off...

Page 24: ...ordance with the kW rating and system pressure 5 4 3 Water temperature The maximum permissible water ow temperature is 90 C If the limit thermostat is triggered at 97 C the boiler will switch off and...

Page 25: ...in the return line of the secondary part of the system In order to guarantee a properly working system and long life one should remove suspended and corrosive particles by installing a suitable lter s...

Page 26: ...ion at minimum 6 Output status burner load P17 7 Actual required parameter value W2 Service operation at maximum 8 Error code parameter number burner load P9 9 Status inputs Desired load required by t...

Page 27: ...t The new ow temperature will now be active Close the lid Set the required hot water temperature for hot water operation This is only applicable if the hot water mode is being used Open the lid Turn t...

Page 28: ...upted The resistance value measured by the ue temperature sensor lies outside the range of 10 and 126 C Repair the fault and press reset An external safety device connected to the terminals 1 3 has be...

Page 29: ...tion to t B The boiler is out of operation and only comes into operation due to the automatic frost protec tion system Using the rotary selector switch set the type of operation to K C Switch off the...

Page 30: ...lue for full load Reference value for CO2 Types R30 45 R30 65 R30 85 and R30 120 8 8 0 2 for natural gas G20 G25 9 8 0 2 for propane G31 Type R30 100 9 4 0 2 for natural gas G20 G25 10 4 0 2 for propa...

Page 31: ...by using the setting screws Type Diameter of throttle ring R30 45 6 8 mm R30 65 6 0 mm R30 85 6 0 mm R30 100 6 8 mm Remove the measuring equipment and re t the case The boiler is now ready for operat...

Page 32: ...ges Check the combustion Calibrated measuring equipment should be used to carry out gas air and ue gas measurements 8 4 Cleaning the burner and the heat exchanger The burner can be cleaned on both sid...

Page 33: ...7 1 0914 CO easured 2 Conversion factors For NOx N 1 1 ppm 2 05 mg m3 1 759 mg kWh 0 498 mg MJ For CO N 1 1 ppm 1 24 mg m3 1 064 mg kWh 0 298 mg MJ Example Measured values for an environmentally frie...

Page 34: ...oss calori c value o Fuel ef ciency at the nett calori c value CO2 The volume of CO2 in the ue gas O2 The volume of O2 in the ue gas A The quantity of condensed water in the appliance per m3 gas in kg...

Page 35: ...Doc653 30CV02A 31...

Page 36: ...32 Doc653 30CV02A...

Reviews: