Doc653/30CV02A
1
R30 Technical data
Type
R30/45
R30/65
R30/85
R30/100
R30/120
Nominal heat output (80/60
o
C)
Nominal heat output (40/30
o
C)
Heat input, gcv (H
s
)
Heat input, ncv (H
i
)
kW
kW
kW
kW
5.6-39.2
6.3-43.0
6.4-44.4
5.8-40.0
8.3-59.2
9.2-65.0
9.5-67.4
8.6-60.7
15.6-77.8
17.0-85.0
17.7-88.8
16.0-80.0
17.6-88.2
19.2-96.3
19.9-99.9
18.0-90.0
21.9-109.8
24.0-120.0
25.0-124.8
22.5-112.4
Gas consumption Natural gas H
(10.9 kWh/m
3
)
Propane (
24.65 kWh/m
3
)
Gas inlet pressure
Natural gas (min./max.)
Propane (min./max.)
m
3
/h
m
3
/h
mbar
mbar
0.5-3.7
0.2-1.6
17/20
30/50
0.8-5.6
0.3-2.5
17/20
30/50
1.4-7.3
0.6-3.2
17/20
30/50
1.6-8.2
0.7-3.6
17/20
30/50
2.1-10.3
0.9-4.6
17/20
30/50
Maximum water temperature of central
heating system
Maximum operating pressure
Water content
Water resistance (∆T= 20°C)
Excess head of the boiler pump (∆T= 20°C)
°C
bar
litre
kPa
kPa
90
6
5.1
14
26
90
6
6.6
20
29
90
6
8.4
25
15
90
6
10.3
28
24
90
6
12.0
30
12
Connection for fl ue outlet
D
Connection for air inlet
D1
Gas connection
G
Water connection W
(int)
W (ext)
Condensate drain (
∅
outer
)
mm
mm
mm
80
80
R
3
⁄
4
"
Rp1"
R1
1
⁄
4
"
25
80
80
R
3
⁄
4
"
Rp1"
R1
1
⁄
4
"
25
100
100
R
3
⁄
4
"
Rp1"
R1
1
⁄
4
"
25
100
100
R
3
⁄
4
"
Rp1"
R1
1
⁄
4
"
25
100
100
R
3
⁄
4
"
Rp1"
R1
1
⁄
4
"
25
Electrical supply
Frequency
Fuse protection
V
Hz
A
230
50
6
230
50
6
230
50
6
230
50
6
230
50
6
Maximum power consumption (excl. pump)
Maximum power consumption (incl. pump)
Insulation
W
W
97
190
IPX4D
98
230
IPX4D
123
255
IPX4D
130
325
IPX4D
215
410
IPX4D
Boiler weight, empty, ± 5%
kg
45
55
65
80
90
Table 1
Technical data R30
Summary of Contents for ECONOFLAME R30
Page 35: ...Doc653 30CV02A 31...
Page 36: ...32 Doc653 30CV02A...