STIENEN PL-9500 User Manual Download Page 24

 

Page 24 of 31

 

TIME SCHEDULES 

 

 

 

 

See “Master timer”. 

 

 

 

DOSAGE TIMER (WATER / FEED / SEQUENTIAL TIMERS) 

The timer output of a dosage timer is linked to a counter input. This enables the water and/or feed intake to be 

limited. If the intake is too low, the controller can generate a “dosage alarm” and stop the dosing of water 

and/or feed. If the installer has set the “Dosage” setting to no, the dosage timer will act as a “normal” timer. 

 

If the installer has switched “Auto. partition period” off: possibility to manually distribute the total daily amount 

of the feed, for example, over the number of periods set. 

 

SETTINGS 

 

 

 

 

The curve can be used for age-dependent variation of: 

● 

The amount (water/feed) per animal. 

● 

The time schedules. 

 

If the dosage timer is linked to the master timer: the times are related to the 

times of the master timer (after this there is still a possibility to correct the 

starting and end times (+/– 8 hours, see page 23). 

 

Sequential timers (“Feed chain” and “Rinse timer”) can also be found under this 

menu option. 

 

Sequential timers activate the different outputs assigned to the timer in turn, after each other. An output is not 

activated until the preceding output is no longer active. The different actions carried out in turn are also called 

'phases' or 'steps'. 

 

On a sequential timer, you can only set the start time; the end time is determined by the total pulse pause time 

and the number of outputs. 

 

Feed chain 

The outputs that have been set are driven sequentially (one by one) at the start time. You can use the external 

input to temporarily “freeze” (stop) the time. If the external input is active, the time is stopped (interrupted) 

temporarily. The time will start running again from the point where it was interrupted, as soon as the external 

input is deactivated. 

 

Feed chain: 

“On”  

: Local time schedule. 

“Slave”  : The On/Off times of the timer are based on the switching times of the “Master 

timer”. 

Time schedule: 

Have the timer switch on and off based on a pre-programmed time schedule. Enter the 

time schedule of your choice (1..9) at “Time schedule”. 

 

“On without time schedule”  : Fill in the start and end times locally. 
“On with time schedule” 

: The settings are a copy of the settings of the time schedule 

that has been set. You cannot change the number of periods 

or the start and end times in this screen. 

“Slave” 

: The settings are a copy of the settings of the master timer. 

You can affect the times locally by entering a time that 

differs from that for the master timer under “Begin”. 

Current status: 

Display of current status of the “Feed chain” timer. The current status is replaced by 

“Output” followed by the active output, the status of the active output and the period 

time. 

Output

 

 

 

Pulse: 

Time that an output is switched on. 

Pause: 

Waiting time before the following input is switched on. 

 

Rinse timer 

The rinse timer can be used for several purposes, e.g. rinsing the water pipes before the drinkers are activated 

again in order to prevent Legionella in the water system. The rinse timer is set in accordance with the “Feed 

chain” timer. 

 

Summary of Contents for PL-9500

Page 1: ...USER MANUAL PL 9500 i POULTRY COMPUTER EN Stienen BE PL 9500 G EN02000 PL 9500 PL 9500 i...

Page 2: ...questions Be sure to have all necessary data at hand To ensure a speedy solution to the malfunction and to avoid any misunderstandings it is advisable to note down the cause and the circumstances in w...

Page 3: ...12 House 12 Main ventilation 12 Auxiliary ventilation 13 Heat exchanger 13 Inlet flaps 14 Heating 14 Cooling 15 Temperature controls 16 Miscellaneous 16 FEED 17 Feed weighing 17 Feed mixture 20 Per d...

Page 4: ...p of the fixed socket outlet until you hear it click lock Application notes Animal weighing PL95IAW N ENxxxxx Central exhaust PL95ICE N ENxxxxx Data communication between poultry computers PL95IDC N E...

Page 5: ...gin screen Touch open numerical keypad Enter your login code and touch the key CONTROL KEYS return to the overview screen HOME select next previous screen select input position select option next prev...

Page 6: ...add a breakpoint to remove a breakpoint from a list curve timer if a setting is followed by the Link symbol use this link to jump to another screen The Link back symbol will then show in the right han...

Page 7: ...1 99 Analogue output with a range of 2 10V with position feedback signal Among these are modules for controlling an EGM 100CA or EGM 250CA Air inlet flap H 1 99 MCA flap a wind compensated air inlet f...

Page 8: ...ions growth curve compensations alarms Heating settings growth curve alarms Coolers settings options growth curve compensations alarms Temperature controls settings alarms Miscellaneous humidification...

Page 9: ...you wish to add to the favourites bar Touch the icon of the menu item until the add window appears Touch OK to add the menu item to the favourites bar DELETE MENU ITEM FROM FAVOURITES BAR Touch the i...

Page 10: ...Call up this week s weekly summary of mutations Call up last week s weekly summary of mutations If two animal groups are present call up the mutations per animal group ENTRY DATA Changing entry data T...

Page 11: ...he pipe s during the pre set period before an alarm is generated If the counter is linked to a dosing timer the dosing timer output is also switched off CLEAR Clear all counters See also Counter HOUR...

Page 12: ...th compensation and compensation maximum ventilation are mutually exclusive Compensation minimum and maximum ventilation Meteo compensation ALARMS Available alarms House temperature RH measurement RH...

Page 13: ...n Max ventilation Show measurements calculation of the above parameters OPTIONS Display the status of the step control if installed GROWTH CURVE Set growth curve auxiliary ventilation Temperature Min...

Page 14: ...h curve per ventilation group except for the flaps that have been set to Tunnel Temperature Min Max ventilation COMPENSATIONS Set influence of RH and CO2 compensation ALARMS Switch the alarm on off fo...

Page 15: ...is set to Off to prevent soaking from starting immediately after the house has been set to Not in use GROWTH CURVE Set temperature growth curve per cooling COMPENSATIONS Reduction function Prevent th...

Page 16: ...midification control On Off Set the percentage of the relative humidity below which the control must be active If Cooling 1 and Humidification are connected to the same output the output is controlled...

Page 17: ...the amount filled After confirming your input the amount filled is automatically added to the silo contents and Filled is cleared Silo state The status changes to empty if any of these events occur A...

Page 18: ...is taken again an alternative component has been selected Silo order for the component has not been filled in the feed type occurs in the feed mixture of today Enter the silo sequence with the corres...

Page 19: ...switched off reset the system will try to finish the active portion Tare alarm Deactivate the tare alarm on the PFB feed weigher will be switched off alarm code 2 AL2 Supply alarm Deactivate the suppl...

Page 20: ...lues the percentages shown can differ approx 0 1 from the actual calculated percentages CURVE There is a curve to gradually have the feed mixture changed automatically as time passes This curve has a...

Page 21: ...per animal if animal data is available The poultry computer can show the details of the past 7 days PER PERIOD WATER FEED Dosage timer request the amount dosed water or feed per animal per period The...

Page 22: ...edule activated automatically depending on the ages of the animals Growth curves time schedules is followed by the current time schedule see also Time schedules LOCAL TIME SCHEDULE FIX TIME SCHEDULE Y...

Page 23: ...the time period during which the light intensity should be intensified or dimmed The desired light intensity at the end of the intensification or dimming period Slave If the light timer is linked to t...

Page 24: ...he outputs that have been set are driven sequentially one by one at the start time You can use the external input to temporarily freeze stop the time If the external input is active the time is stoppe...

Page 25: ...m amount to be dosed as a percentage relative to the total amount to be dosed If this percentage is not achieved a dosing alarm will be generated MISCELLANEOUS ON OFF TIMERS NEST BOX TIMER SETTINGS TI...

Page 26: ...eferably use the Off alarm retard function to solve a problem Installation errors such as Output already assigned Incorrect output type Input already assigned etc have to be solved first before puttin...

Page 27: ...and or between E and S is not between 2 0 V and 3 0 V Check the voltage Check the wiring Outside sensor faulty Value measured by outside temperature sensor 50 0 C or 50 0 C CO2 too low The CO2 measur...

Page 28: ...arge hatch closed Discharge hatch opened Valve not opened closed after 10 seconds although it was sent a drive signal to open close it Maximum supply alarm The counter exceeds the maximum setting with...

Page 29: ...s 2 The Conflicting periods error message occurs if 1 or more feed dosing timers have to be active at the same time Potentiometer faulty The value measured by the potentiometer is outside the limits E...

Page 30: ...calculated Feed weigher xx xx alarm code from PFB feed weigher for further information see the manual with the PFB feed weigher Invalid feed weigher Incompatible software version on the PFB feed weig...

Page 31: ...the negative pressure we advise you to check the operation of the filters and flaps Check for air pressure leakage in the house Air leaks can lead to draughts and in summer they can result in unwanted...

Reviews: