STIENEN PL-9500 User Manual Download Page 28

 

Page 28 of 31

 

 

Alarm code 

Description 

Wrong terminal setting 

Faulty allocation. The function you have assigned to the terminal is not 

supported by the module. 

No outside sensor 

The control installed requires an outdoor sensor but no outdoor sensor has 

been installed 

No communication address 

Missing device address PL-9500 and/or PFB. 

No pressure control 

The control installed requires a pressure control but no pressure control has 

been installed 

No weight reduction 

The weight in the mixer does not decrease at all or does not decrease enough 

during the “Unload mixer” status; check the mixer/discharge auger. 

No input assigned 

No input terminal number entered 

No PFB 

An input/output refers to the PFB feed weigher but no PFB feed weigher has 

been installed. 

No silo weigher 

The counter has been set to “PSW-1” but no PSW-1 has been installed. 

No silo number or an incorrect silo number has been entered for the counter. 

No info from houses 

A central control installed on the climate control has not received any data 

from the external controller to control the central control (e.g. an incorrectly 

set feed weighing computer or an incorrect central control number etc.). 

 

If the PL-9500 is connected to a feed system: 

 

The animal group at the PL-9500 has not been set to communication. 

 

You use dosing timers and the “Counter in group” setting of one of the 

relevant counters has been set to “Both groups”. This is not allowed; 

choose “Animals 1” or “Animals 2”. 

 

Software version PL-9500 is too old, update software. 

 

House not in use. 

No output assigned 

No output terminal number entered 

No feed weigher 

The counter has been set at “PFB feed” or “PFB water” but no PFB feed 

weigher has been installed. 

Input already assigned 

The input has been assigned to two or more controls. 

Discharge hatch closed 

Discharge hatch opened 

Valve not opened/closed after 10 seconds although it was sent a drive signal 

to open/close it. 

Maximum supply alarm 

The counter exceeds the maximum setting within the time set. 

Meteo faulty 

 

The result measured by the meteo station (wind direction, wind speed 

and/or rain level) is outside the preset limits (these limits depend on the 

type of sensor ME-54 or PL-MWA). 

 

Bridging wire is missing, PL-Meteo without a rain sensor; further 

information on the bridging wire can be found in the PL-Meteo annex. 

Module x not installed 

 

The module number set for the terminal does not exist 

 

Poor or no connection between PL-9200-MODULE and module. 

 

The connection cable between the PL-9200-MODULE and the PL-9200 

bottom PCB is missing or is loose. 

Module x not responding 

Module address not found, check the settings on the module 

Module x reset alarm 

Module continues to reset due to a fault, check the module 

Not closed 

The nest box is still open after the propagation time (i.e. running time) has 

elapsed. 

Not calibrated 

The scale has not been calibrated (the weighing scales are factory calibrated 

as standard). The weighing scale must then be returned to the factory to be 

calibrated. 

Not open 

The nest box is not open after the propagation time (i.e. running time) has 

elapsed. 

Unknown terminal type 

This type of terminal does not exist 

Invalid combination 

Both the dosing timer and the animal group have been set to 

“communication”. This is not allowed. You can either set only dosing timers via 

communication (augers) or you can send the animal data via communication 

(valves). 

Invalid component 

A component in the “Silo assignment” is accompanied by a silo number that 

does not contain the right component (the component in one of the silos has 

changed). 

Invalid group of animals 

The feed weigher is set to PFV-92xx, the feed counter has “Both groups” as 

the setting for “Counter in group”. However, the PFV-92xx can be assigned to 

only one animal group. 

 

Summary of Contents for PL-9500

Page 1: ...USER MANUAL PL 9500 i POULTRY COMPUTER EN Stienen BE PL 9500 G EN02000 PL 9500 PL 9500 i...

Page 2: ...questions Be sure to have all necessary data at hand To ensure a speedy solution to the malfunction and to avoid any misunderstandings it is advisable to note down the cause and the circumstances in w...

Page 3: ...12 House 12 Main ventilation 12 Auxiliary ventilation 13 Heat exchanger 13 Inlet flaps 14 Heating 14 Cooling 15 Temperature controls 16 Miscellaneous 16 FEED 17 Feed weighing 17 Feed mixture 20 Per d...

Page 4: ...p of the fixed socket outlet until you hear it click lock Application notes Animal weighing PL95IAW N ENxxxxx Central exhaust PL95ICE N ENxxxxx Data communication between poultry computers PL95IDC N E...

Page 5: ...gin screen Touch open numerical keypad Enter your login code and touch the key CONTROL KEYS return to the overview screen HOME select next previous screen select input position select option next prev...

Page 6: ...add a breakpoint to remove a breakpoint from a list curve timer if a setting is followed by the Link symbol use this link to jump to another screen The Link back symbol will then show in the right han...

Page 7: ...1 99 Analogue output with a range of 2 10V with position feedback signal Among these are modules for controlling an EGM 100CA or EGM 250CA Air inlet flap H 1 99 MCA flap a wind compensated air inlet f...

Page 8: ...ions growth curve compensations alarms Heating settings growth curve alarms Coolers settings options growth curve compensations alarms Temperature controls settings alarms Miscellaneous humidification...

Page 9: ...you wish to add to the favourites bar Touch the icon of the menu item until the add window appears Touch OK to add the menu item to the favourites bar DELETE MENU ITEM FROM FAVOURITES BAR Touch the i...

Page 10: ...Call up this week s weekly summary of mutations Call up last week s weekly summary of mutations If two animal groups are present call up the mutations per animal group ENTRY DATA Changing entry data T...

Page 11: ...he pipe s during the pre set period before an alarm is generated If the counter is linked to a dosing timer the dosing timer output is also switched off CLEAR Clear all counters See also Counter HOUR...

Page 12: ...th compensation and compensation maximum ventilation are mutually exclusive Compensation minimum and maximum ventilation Meteo compensation ALARMS Available alarms House temperature RH measurement RH...

Page 13: ...n Max ventilation Show measurements calculation of the above parameters OPTIONS Display the status of the step control if installed GROWTH CURVE Set growth curve auxiliary ventilation Temperature Min...

Page 14: ...h curve per ventilation group except for the flaps that have been set to Tunnel Temperature Min Max ventilation COMPENSATIONS Set influence of RH and CO2 compensation ALARMS Switch the alarm on off fo...

Page 15: ...is set to Off to prevent soaking from starting immediately after the house has been set to Not in use GROWTH CURVE Set temperature growth curve per cooling COMPENSATIONS Reduction function Prevent th...

Page 16: ...midification control On Off Set the percentage of the relative humidity below which the control must be active If Cooling 1 and Humidification are connected to the same output the output is controlled...

Page 17: ...the amount filled After confirming your input the amount filled is automatically added to the silo contents and Filled is cleared Silo state The status changes to empty if any of these events occur A...

Page 18: ...is taken again an alternative component has been selected Silo order for the component has not been filled in the feed type occurs in the feed mixture of today Enter the silo sequence with the corres...

Page 19: ...switched off reset the system will try to finish the active portion Tare alarm Deactivate the tare alarm on the PFB feed weigher will be switched off alarm code 2 AL2 Supply alarm Deactivate the suppl...

Page 20: ...lues the percentages shown can differ approx 0 1 from the actual calculated percentages CURVE There is a curve to gradually have the feed mixture changed automatically as time passes This curve has a...

Page 21: ...per animal if animal data is available The poultry computer can show the details of the past 7 days PER PERIOD WATER FEED Dosage timer request the amount dosed water or feed per animal per period The...

Page 22: ...edule activated automatically depending on the ages of the animals Growth curves time schedules is followed by the current time schedule see also Time schedules LOCAL TIME SCHEDULE FIX TIME SCHEDULE Y...

Page 23: ...the time period during which the light intensity should be intensified or dimmed The desired light intensity at the end of the intensification or dimming period Slave If the light timer is linked to t...

Page 24: ...he outputs that have been set are driven sequentially one by one at the start time You can use the external input to temporarily freeze stop the time If the external input is active the time is stoppe...

Page 25: ...m amount to be dosed as a percentage relative to the total amount to be dosed If this percentage is not achieved a dosing alarm will be generated MISCELLANEOUS ON OFF TIMERS NEST BOX TIMER SETTINGS TI...

Page 26: ...eferably use the Off alarm retard function to solve a problem Installation errors such as Output already assigned Incorrect output type Input already assigned etc have to be solved first before puttin...

Page 27: ...and or between E and S is not between 2 0 V and 3 0 V Check the voltage Check the wiring Outside sensor faulty Value measured by outside temperature sensor 50 0 C or 50 0 C CO2 too low The CO2 measur...

Page 28: ...arge hatch closed Discharge hatch opened Valve not opened closed after 10 seconds although it was sent a drive signal to open close it Maximum supply alarm The counter exceeds the maximum setting with...

Page 29: ...s 2 The Conflicting periods error message occurs if 1 or more feed dosing timers have to be active at the same time Potentiometer faulty The value measured by the potentiometer is outside the limits E...

Page 30: ...calculated Feed weigher xx xx alarm code from PFB feed weigher for further information see the manual with the PFB feed weigher Invalid feed weigher Incompatible software version on the PFB feed weig...

Page 31: ...the negative pressure we advise you to check the operation of the filters and flaps Check for air pressure leakage in the house Air leaks can lead to draughts and in summer they can result in unwanted...

Reviews: