Page 7 of 31
TERMINAL NUMBER IN-/OUTPUTS
The terminal number of an input/output consists of the module address, the type of input/output and a 2-digit
serial number.
Type in-/output
Letter Serial number Description
0-10V output
A
1-99
Analogue output with a range of 0-10V or 10-0V.
Relays output
B
1-99
Relay contact output (this does not include: alarm relay,
pulse outputs etc.)
Digital output
C
1-99
Opto coupler output (Max. 35Vdc 30mA).
Open-/close control
D
1-99
Open-/close control with position feedback signal.
This includes e.g. flaps with position feedback signal.
30-230Vac output
F
1-99
Analogue output with a range of 30-230Vac or 230-30Vac.
2-10V output
G
1-99
Analogue output with a range of 2-10V with position
feedback signal. Among these are modules for controlling an
EGM-100CA or EGM-250CA
Air inlet flap
H
1-99
MCA flap, a wind compensated air inlet flap
Temperature sensor
K
1-99
This includes all types of temperature sensor fitted with 10K
NTC resistor (N10B, BV10B etc.)
0-10V input
L
1-99
Analogue input with a measuring range of 0-10V. To connect
measuring sensors such as RH, CO2, pressure etc.
Digital input
M
1-99
This includes measuring fans, counter contacts etc.
Meteo station
N
1-99
Module on which a wind speed meter, wind direction and a
rain sensor can be connected to.
If the keyboard symbol lights up, touch the symbol to display one of the following virtual keyboards
on the screen.
Set input terminals
Set output terminals
and
: decrease/increase setting.
MODULE SCREEN
Input/output already assigned.